Altronix 6062 Manual

Altronix 6062 Manual

Multi-purpose timer

Advertisement

Quick Links

Overview:
Model 6062 programmable timer is suitable for many functions that require a timed operation e.g. Access Control Applications, Siren/Bell
Cut Off Module, Dialer Delay, Guard Tour Supervisory Timer, etc. Some optional functions include: One Shot, Delayed Release, Delayed
Operate, Delayed Pulse and Pulser/Flasher. A new feature has been added which provides a momentary relay activation at the end of a
desired timing cycle. This feature eliminates the need for having to use two (2) timers to achieve this function. Another new feature will
cancel (interrupt) timing cycle and reset timer if desired.
Specifications:
• 12VDC or 24VDC operation is selectable.
• Quick and extremely accurate time range adjustment from 1 sec. to 60 min.
• LED indicates relay is energized.
• Form "C" relay contacts are 8 amp at 120VAC/28VDC.
• Current Draw: Stand-by 3mA, Relay Energized 40mA.
• Triggers via positive DC (+) voltage, dry contact closure, or removal of contact closure.
• Selectable relay activation at the start or end of the timing cycle.
• One (1) second momentary relay activation at the end of
the timing cycle (eliminates the need to use two (2) timers for this function).
• Built-in reset feature which cancels timing cycle.
• Repeat (pulser/flasher) mode.
• Snap Trac compatible (order Altronix model #ST3)
• DIN Rail Mount version available (order Altronix model #DTMR1).
Board dimensions: 3"L x 2.5"W x .75"H (approximate)
Installation Instructions:
1. Mount 6062 in desired location/enclosure.
2. Set proper DC Input Voltage Dip Switch 3: 12VDC ON, 24VDC OFF.
3. Refer to Dip Switch Selection and Jumper Selection Tables for desired functions (e.g.: Timing, Trigger, Pulse)
4. Measure DC input voltage before powering device to ensure proper operation.
5. Refer to Terminal Identification Table and Typical Applications fig. 1 thru fig. 8. for desired wiring connections.
Note: When triggering via a N.O. (normally open), momentary or maintained trigger, connect the dry contact trigger to
Pos (+) and TRG terminals.
When triggering via a N.C. (normally closed), momentary or maintained trigger, connect the trigger to Neg. (-) and TRG
terminals and install a resistor [for 12VDC - 2K (2,000 ohm) or for 24VDC - 4.7K (4,700 ohm)] between the Pos (+) and TRG
terminals (Fig. 8).
Dip Switch Selection Table:
Dip #
Off
1
Relay energizes at start of timing cycle.*
2
1-60 minutes timing range. (adjust trimpot)
3
24VDC operating voltage.
4
Timing begins immediately upon trigger input.
* When relay energizes (LED is on) [N.O. & C] switch from open to close and [N.C. & C] switch from close to open.
Jumper Selection Table:
Number
Function/Description
J1
Cutting J1 selects the pulser/flasher mode. Relay will flip ON and OFF
continuously in equally set timed intervals when timer is powered up.
J2
Cutting J2 puts timer in delayed output mode. Relay will pulse for 1 second at
the end of a preset timing cycle. *Dip Switch 1 must be ON for this function.
J3
6062 will go through an initial timing cycle when first powered up unless J3 is cut.
If J3 is cut, timing can only be initiated via TRG terminal
Terminal Identification:
Terminal
Function/Description
Legend
TRG
Applying a positive voltage will activate timing cycle.
Trigger voltage range: 7-12VDC at 12 volt setting, 15-24VDC at 24 volt setting.
--, +
Connect 12 or 24VDC filtered and regulated voltage. Refer to Dip Switch Selection Table for voltage setting.
N.O., C, N.C.
Dry form "C" relay contacts are rated 8 amp at 120VAC/28VDC.
6062 - Multi-purpose Timer
On
Relay energizes at the end of timing cycle.*
1-60 seconds timing range. (adjust trimpot)
12VDC operating voltage.
Timing starts after removal of trigger input.

Advertisement

loading

Summary of Contents for Altronix 6062

  • Page 1 6062 - Multi-purpose Timer Overview: Model 6062 programmable timer is suitable for many functions that require a timed operation e.g. Access Control Applications, Siren/Bell Cut Off Module, Dialer Delay, Guard Tour Supervisory Timer, etc. Some optional functions include: One Shot, Delayed Release, Delayed Operate, Delayed Pulse and Pulser/Flasher.
  • Page 2 Switch #4 is not used in this application. Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. MEMBER II6062 - Rev. 120104...