Model 6062 programmable timer is suitable for many functions that require a timed operation e.g. Access Control Applications,
Siren/Bell Cut Off Module, Dialer Delay, Guard Tour Supervisory Timer, etc. Some optional functions include: One Shot, Delayed
Release, Delayed Operate, Delayed Pulse and Pulser/Flasher. A new feature has been added which provides a momentary relay acti-
vation at the end of a desired timing cycle. This feature eliminates the need for having to use two (2) timers to achieve this function.
• 12VDC or 24VDC operation is selectable.
• Quick and extremely accurate time range adjustment from
1 sec. to 60 min.
• LED indicates relay is energized.
• Form "C" relay contacts are 8 amp at 120VAC/28VDC.
• Current Draw: Stand-by 3mA, Relay Energized 40mA.
• Triggers via positive DC (+) voltage, dry contact closure,
or removal of contact closure.
• Selectable relay activation at the start or end of the
timing cycle.
1. Mount 6062 in desired location/enclosure.
2. Set proper DC Input Voltage Dip Switch 3: 12VDC ON, 24VDC OFF.
3. Refer to Dip Switch Selection and Jumper Selection Tables for desired functions (e.g.: Timing, Trigger, Pulse)
4. Measure DC input voltage before powering device to ensure proper operation.
5. Refer to Terminal Identification Table and Typical Applications fig. 1 thru fig. 8. for desired wiring connections.
Note: When triggering via a N.O. (normally open), momentary or maintained trigger, connect the dry contact trigger to Pos (+)
and TRG terminals. When triggering via a N.C. (normally closed), momentary or maintained trigger, connect the trigger to Neg. (-)
and TRG terminals and install a resistor [for 12VDC - 2K (2,000 ohm) or for 24VDC - 4.7K (4,700 ohm)]
between the Pos (+) and TRG terminals (Fig. 8).
6. Enable the reset features:
- Cut J3 when power is removed the timer will reset and not re-trigger when power is restored unless a new trigger is applied.
Note: The closed trigger and delayed pulse options will not operate if the reset feature is desired.
Dip # Off
1
Relay energizes at the start of timing cycle.*
2
1-60 Minutes timing range (trimpot adjustable).
3
24VDC operating voltage.
4
Timing begins immediately upon trigger input.
* When relay energizes (LED is on) [N.O. & C] switch from open to close and [N.C. & C] switch from close to open.
Number Function/Description
Cutting J1 selects the pulser/flasher mode. Relay will flip ON and OFF
J1
continuously in equally set timed intervals when timer is powered up.
Cutting J2 puts timer in delayed output mode. Relay will pulse for 1 second at
J2
the end of a preset timing cycle. *Dip Switch 1 must be ON for this function.
6062 will go through an initial timing cycle when first powered up unless J3 is cut.
J3
If J3 is cut, timing can only be initiated via TRG terminal.
Terminal
Function/Description
Legend
Applying a positive voltage will activate timing cycle.
TRG
Trigger voltage range: 7-12VDC at 12 volt setting, 15-24VDC at 24 volt setting.
--- , +
Connect 12 or 24VDC filtered and regulated voltage. Refer to Dip Switch Selection Table for voltage setting.
N.O., C, N.C. Dry form "C" relay contacts are rated 8 amp at 120VAC/28VDC.
6062 - Multi-purpose Timer
Overview:

Specifications:

Installation Instructions:

Dip Switch Selection Table:
Jumper Selection Table:
Terminal Identification:
• One (1) second momentary relay activation at the end of
the timing cycle (eliminates the need to use two (2) timers
for this function).
• Built-in reset feature which cancels timing cycle.
• Repeat (pulser/flasher) mode.
• Snap Track compatible (order Altronix model #ST3)
• DIN Rail Mount version available
(order Altronix model #DTMR1).
Board dimensions: 3"L x 2.5"W x .75"H (approximate)
On
Relay energizes at the end of timing cycle.*
1-60 Seconds timing range (trimpot adjustable).
12VDC operating voltage.
Timing starts after removal of trigger input.

Advertisement

loading

Summary of Contents for Altronix 6062

  • Page 1: Specifications

    6062 - Multi-purpose Timer Overview: Model 6062 programmable timer is suitable for many functions that require a timed operation e.g. Access Control Applications, Siren/Bell Cut Off Module, Dialer Delay, Guard Tour Supervisory Timer, etc. Some optional functions include: One Shot, Delayed Release, Delayed Operate, Delayed Pulse and Pulser/Flasher.
  • Page 2 24VDC - 4.7K (4,700 ohm)] must be installed as shown (resistor not supplied). Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056 web site: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A. MEMBER II6062 - Rev. 032211 C22K...