M a i n P r o g r a m m i n g - C o n t i n u e d
M a i n P r o g r a m m i n g - C o n t i n u e d
Return to the beginning of the set up menu by pressing the button S1.
To exit the menus
1. After the selection, the menu will automatically be closed whether the modified value is stored or not.
2. It is possible to exit the menu anytime by pressing the buttons S1 and S2 simultaneously.
3. If no button is pressed for 30 seconds, the menu will be closed automatically.
Error message
1. Flashing display of the actual pressure: measured pressure outside of range.
2. Flashing of the display during the programming: An invalid value was entered.
Examples: Switching point above/below the adjustment range, reset point above/below the adjustment range,
reset point above the switching point, analog output span is samller than 20% of the adjustment range
filter more than 2s. When this happens, the buttons are locked for 3s and the switch takes over the next possible value.
Select the switching type of the first switching output.
nPn:
n-switching
Only for the version with analog output!
PnP:
p-switching
Select the pressure value of the analog
output at 4mA/0V.
Select the switching function of the first switching output.
hYSt:
Hysteresis
Only for the version with analog output!
GAtE:
Gate Function
Select the pressure value of the analog
output at 20mA/10V.
Select the first reset point.
Select output filters
Select delay time of the first switching output.
Range:
Resolution: 0.01s
Range:
0.00 ... 99.99s
Grading:
Resolution:
0.01s
Only for the version with two switching points!
Select the second switching point.
Authorization for the user.
Only for the version with two switching points!
The user has the permission
Select delay time of the second switching output.
YES:
To program
Range:
0.00 ... 99.99s
Resolution:
NO:
0.01s
To not program
Only for the version with two switching points!
the switching output in the user menu
Select the contact function of the second switching output.
Save the previous changes.
ncLs:
Normally closed contact
YES:
Save
noPn:
Normally open contact
NO:
Not Save
Only for the version with two switching points!
returns to the actual pressure indication afterwards.
Select the switching type of the second switching output.
nPn:
n-switching
PnP:
p-switching
Only for the version with two switching points!
Select the switching function of the second switching output.
hYSt:
Hysteresis
GAtE:
Gate function
Only for the version with two switching points!
Select the second reset point.
Only for the version with two switching points!
Select the delay time of the second reset point.
Range:
0.00 ... 99.99s
Resolution:
0.01s
9
8
9
0.00...2.00s
Step Size
Range
10ms
0.00...0.2s
50ms
0.2 ...1.0s
100ms
>1.0s