TECHNICAL DATA
CABLE GLAND TYPE
: PXSS2K
INGRESS PROTECTION
: IP66, IP67, IP68
PROCESS CONTROL SYSTEM
: BS EN ISO 9001
: ISO/IEC 80079-34:2011
EXPLOSIVE ATMOSPHERES CLASSIFICATION
ATEX CERTIFICATION No
: SIRA13ATEX1072X, SIRA13ATEX4078X
ATEX CERTIFICATION CODE
:
II 2 GD, II 1D, Ex d IIC Gb, Ex e IIC Gb, Ex ta IIIC Da
:
II 3 G Ex nR IIC Gc,
IM2 Ex d I Mb, Ex e I Mb
IECEx CERTIFICATION No
: IECEx SIR.13.0027X
IECEx CERTIFICATION CODE
: Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb
cCSAus CERTIFICATION No.
: 2288626
cCSAus CERTIFICATION CODE
: Class I, Groups A, B, C and D; Class II, Div. 2, Groups F and G; Class III, Div. 2; Type 4X; Oil Resistance II
: Class I, Zone 1 AEx d IIC Gb, AEx e IIC Gb, Class I, Zone 2 AEx nR IIC Gc, Class I, Zone 20 AEx ta IIIC Da
UL CERTIFICATION FILE
: E201188B, E253914
UL CERTIFICATION CODE
: Class I, Div 2, Groups A,B,C,D; Class II, Div 2, Groups F,G, Class I, Zone 1 AEx d IIC, AEx e II
(Code details depends upon application - please see certificate)
INSTALLATION INSTRUCTIONS
Installation should only be performed by a competent person using the correct tools. Read all instructions before beginning installation.
SPECIAL CONDITIONS FOR SAFE USE
1. According to the CEC wiring code, connectors with metric threads are only suitable for Areas Classified in ZONES unless fitted with an approvedMetric to NPT thread conversion adaptor.
2. Wiring method for type of cables that can be used in Class I, Div. 1, 2, and Class I, Zone 1, 2, Classified Areas according to 60079-14 installation wiring method restrictions.
3. Shipboard Cables are for use on Marine Platform or shipboards only and are subject to local authorities having jurisdiction on the installation.
4. CAUTION - To reduce the risk of flame propagation, fittings with ISO metric threads require:-
a) 5 full threads engaged for gas groups C and D
b) 10 full threads engaged for gas groups A and B
5. When the connector is supplied with metric entry threads, a CMP Entry Thread Washer should be fitted between the connector and the enclosure
to prevent the ingress of moisture or dust into the enclosure. Thread tape must not be applied to the threads.
6. Before installating the connector, ensure that the connector thread forms and the enclosure thread form are compatible.
ACCESSORIES
The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-
Locknut | Earth Tag | Serrated Washer | Entry Thread (I.P.) Sealing Washer | Shroud *
Available Entry Threads (Alternate Metric Thread
Lengths Available)
Number
of Cores
Standard
Option
Cable
Gland
Size
Min Thread
Thread
Metric
Length
NPT
Length
NPT
Max
(Metric)
(NPT)
20S/16
M20
15.0
1/2"
19.9
3/4"
11
20S
M20
15.0
1/2"
19.9
3/4"
11
20
M20
15.0
1/2"
19.9
3/4"
11
25
M25
15.0
3/4"
20.2
1"
21
32
M32
15.0
1"
25.0
1 1/4"
38
40
M40
15.0
1 1/4"
25.6
1 1/2"
59
50S
M50
15.0
1 1/2"
26.1
2"
89
50
M50
15.0
2"
26.9
2 1/2"
89
63S
M63
15.0
2"
26.9
2 1/2"
115
63
M63
15.0
2 1/2"
39.9
3"
115
75S
M75
15.0
2 1/2"
39.9
3"
140
75
M75
15.0
3"
41.5
3 1/2"
140
90
M90
24.0
3 1/2"
42.8
4"
200
100
M100
24.0
4"
44.0
5"
200
*Note : For material options please add the following suffix to change the Ordering Reference ; Brass (no suffix required), Nickel Plated Brass "5", 316 Grade Stainless Steel "4", Copper Free Aluminium "1"
For NPT options please add the following digits to the material suffix ; 1/2" = 31, 3/4" = 32, 1" = 33, 1 1/4" = 34, 1 1/2" = 35, 2" = 36, 2 1/2" = 37, 3" = 38, 3 1/2" = 39, 4" = 310 (Brass requires prefix "0")
Examples : 32PXSS2K1RA534 = Nickel Plated Brass 1-1/4" NPT, 50SPXSS2K1RA035 = Brass 1-1/2" NPT, 25PXSS2K1RA432 = Stainless Steel 3/4" NPT, 20PXSS2K1RA5 = Nickel Plated Brass M20
Dimensions are displayed in millimetres unless otherwise stated
CMP Products Limited on its sole responsibility declares that the equipment referred to herein conforms to the requirements of the ATEX Directive 2014/34/EU and the following standards:-
EN 60079-0:2012, EN 60079-1:2007, EN 60079-7:2007, EN 60079-15:2010, EN 60079-31:2009, BS 6121:1989, EN 62444:2013
David Willcock - Certification Engineer - (Authorised Person)
CMP Products Limited, Cramlington, NE23 1WH, UK
24th June 2015
0518
Notified Body: Sira Certification Service, Unit 6, Hawarden Industrial Park, Hawarden, CH5 3US, UK
www.cmp-products.com
Diameter
Cable
Combined Ordering
Overall Cable
Across
Across
Over
Bedding
Diameter
Flats
Corners
Conductors
Diameter
(*Brass Metric)
Protrusion
Length
Max
Max
Min
Max
Max
Max
Size
8.6
8.6
3.1
8.6
30.0
33.0
53.1
20S16
11.7
11.7
6.1
11.7
30.0
33.0
53.1
20S
12.6
12.9
6.5
14.0
30.0
33.0
54.2
20
17.5
17.9
11.1
20.0
36.0
39.6
60.0
25
23.6
23.9
17.0
26.3
41.0
45.1
61.1
32
30.0
30.3
22.0
32.1
50.0
55.0
62.4
40
36.6
36.9
29.5
38.2
55.0
60.5
65.2
50S
41.0
41.3
35.6
44.0
60.0
66.0
67.6
50
47.9
48.4
40.1
49.9
70.1
77.1
71.1
63S
53.7
54.0
47.2
55.9
75.0
82.5
70.4
63
59.9
60.2
52.8
61.9
80.0
88.0
75.3
75S
64.3
64.2
59.1
67.9
85.0
93.5
74.9
75
75.3
75.6
66.6
79.4
108.0
118.8
94.8
90
85.6
85.9
76.0
90.9
123.0
135.3
86.3
100
Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS
Tel: +44 191 265 7411 • Fax: +44 1670 715 646
E-Mail: customerservices@cmp-products.co.uk • Web: www.cmp-products.com
Date Printed:
INSTALLATION INSTRUCTIONS FOR
CMP CABLE GLAND TYPE PXSS2K
FOR TERMINATION OF UNARMOURED, BRAIDED CABLES AND EXTRA HARD CORD
USEAGE CABLES FOR USE IN HAZARDOUS LOCATIONS.
INCORPORATING EU DECLARATION OF CONFORMITY TO DIRECTIVE [2014/34/EU]
Reference
Cable
Gland
Shroud
Weight
(Kgs)
Ordering
Type
Suffix
PXSS2K
1RA
PVC06
0.20
PXSS2K
1RA
PVC06
0.20
PXSS2K
1RA
PVC06
0.20
PXSS2K
1RA
PVC09
0.33
PXSS2K
1RA
PVC10
0.39
PXSS2K
1RA
PVC13
0.56
PXSS2K
1RA
PVC15
0.66
PXSS2K
1RA
PVC18
0.73
PXSS2K
1RA
PVC21
1.07
PXSS2K
1RA
PVC23
1.06
PXSS2K
1RA
PVC25
1.30
PXSS2K
1RA
PVC27
1.30
PXSS2K
1RA
PVC31
3.02
PXSS2K
1RA
LSF33
4.00
SCAN FOR INSTALLATION VIDEOS
CABLE GLAND
TYPE PXSS2K
Logo's shown for illustration purposes only. Please check certification for details

Advertisement

loading
Need help?

Need help?

Do you have a question about the PXSS2K and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for CMP PXSS2K

  • Page 1 Dimensions are displayed in millimetres unless otherwise stated CMP Products Limited on its sole responsibility declares that the equipment referred to herein conforms to the requirements of the ATEX Directive 2014/34/EU and the following standards:- EN 60079-0:2012, EN 60079-1:2007, EN 60079-7:2007, EN 60079-15:2010, EN 60079-31:2009, BS 6121:1989, EN 62444:2013...
  • Page 2 INSTALLATION INSTRUCTIONS FOR CMP CABLE GLAND TYPES PXSS2K 5. Bring the cores together again and pack more compound around them to a length and diameter sufficient to fill the compound tube, ending in a taper. CABLE GLAND COMPONENTS Compound 1. Compound 2.