TECHNICAL DATA
CABLE GLAND TYPE
: E** Family of Glands
INGRESS PROTECTION
: IP66, (IP67, IP68 available upon request)
PROCESS CONTROL SYSTEM
: BS EN ISO 9001
: ISO / IEC 80079-34:2001
INSTALLATION INSTRUCTIONS
Installation should only be performed by a competent person using the correct tools. Read all instructions before beginning installation.
CERTIFICATION CONDITIONS
ATEX & IECEx
1.
The E** Type cable glands shall not be used to terminate on braided cables in group I applications.
2.
The glands when used for terminating braided cables are only suitable for fixed installations. Cables must be effectively clamped to prevent pulling or twisting.
1.
Cable gland connectors material may be of brass, aluminum or stainless steel.
CSA us
2.
Connectors with metric entry threads are only suitable for Areas Classified in ZONES unless fitted with an approved Metric to NPT thread conversion adaptor.
3.
According to US (NEC) wiring method for the types of cables that can be used in Class I Zone 1 and 2 Classified Areas, should be in accordance of NFPA-70
installation wiring method restrictions.
1.
Cable gland connectors' material may be of brass, aluminium or stainless steel.
c CSA
2.
These glands are not suitable for use with flameproof enclosures installed in Group IIC atmospheres, which have a volume greater than 2000 cc (2 Litre).
3.
These Glands are for use with Certified Marine Shipboard metal braided cables constructed according to CSA Std. 245 and IEEE45/IEC600092-353 Standards, or
Certified equivalent), for use on Shipboards and Offshore Rigs/platforms only.
4.
"E**" cable gland connectors when installed into Class I, Division 2 Classified Areas, are not suitable to be interfaced with an explosion proof enclosure contain-
ing arcing and sparking devices, unless installed in conjunction with an approved explosion proof sealing fitting.
ACCESSORIES
The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing: Locknut, Earth Tag, Serrated Washer, Entry Thread (I.P.) Sealing Washer, Shroud
Number of turns
to tighten
20S16
20S
20
25S
0.5
13.2
15.9
20.9
22.0
1
12.5
15.3
20.0
21.2
1.5
11.9
14.7
19.0
20.4
2
11.2
14.2
18.1
19.6
2.5
10.5
13.6
17.2
18.8
3
9.8
13.0
16.2
18.0
3.5
9.2
12.4
15.3
17.2
4
8.5
11.8
14.4
16.4
4.5
7.8
11.2
13.4
15.6
5
7.1
10.7
12.5
14.8
5.5
6.5
10.1
12.0
14.0
6
5.8
9.5
Available Entry Threads
Cable
(Alternate Metric Thread Lengths Available)
Bedding
Cable
Diameter
Standard
Option
Gland
Size
Thread
Thread Length
Metric
NPT
Length
NPT
Min
Max
(Metric)
(NPT)
20S16
M20
15.0
1/2"
19.9
3/4"
3.1
20S
M20
15.0
1/2"
19.9
3/4"
6.1
11.6
20
M20
15.0
1/2"
19.9
3/4"
6.5
13.9
25S
M25
15.0
3/4"
20.2
1"
11.1
19.9
25
M25
15.0
3/4"
20.2
1"
11.1
19.9
32
M32
15.0
1"
25.0
1 1/4"
17.0
26.2
40
M40
15.0
1 1/4"
25.6
1 1/2"
22.0
32.1
50S
M50
15.0
1 1/2"
26.1
2"
29.5
38.1
50
M50
15.0
2"
26.9
2 1/2"
35.6
44.0
63S
M63
15.0
2"
26.9
2 1/2"
40.1
49.9
63
M63
15.0
2 1/2"
39.9
3"
47.2
55.9
75S
M75
15.0
2 1/2"
39.9
3"
52.8
61.9
75
M75
15.0
3"
41.5
3 1/2"
59.1
67.9
90
M90
24.0
3 1/2"
42.8
4"
66.6
78.6
100
M100
24.0
3 1/2"
42.8
4"
76.0
90.9
115
M115
24.0
4"
44.0
5"
86.0
97.9
130
M130
24.0
5"
46.8
-
97.0
114.9
Dimensions are displayed in millimetres unless otherwise stated
Order codes shown are for E1FU glands - For e.g. E1FWD glands substitute E1FWD for E1FU - e.g. 20E1FWD1RA
Stepped cone is for single wire armour and grooved cone is for all other armours
CMP Products Limited on its sole responsibility declares that the equipment referred to herein conforms to the requirements of the ATEX Directive 2014/34/EU and the following standards: -
EN60079-0:2012, EN60079-1:2007, EN60079-7:2007, EN60079-15:2010, EN60079-31:2009, BS6121:1989, EN62444:2013
David Willcock – Certification Engineer (Authorised Person)
CMP Products Limited. Cramlington, NE23 1WH, UK
24th June 2015
0518
Notified Body: SIRA Certification Service, Unit 6 Hawarden Industrial Park, Hawarden, CH5 3US, UK
www.cmp-products.com
EXPLOSIVE ATMOSPHERES CLASSIFICATION
ATEX CERTIFICATION No
: SIRA13ATEX1071X, SIRA13ATEX4077X
ATEX CERTIFICATION CODE
: ^ II 2G, II 1D, Ex d IIC Gb, Ex e IIC Gb, Ex ta IIIC Da, ^ II 3G Ex nR IIC Gc,
^ IM2, Ex d I Mb, Ex e I Mb
IECEx CERTIFICATION No
: IECEx SIR.13.0026X
IECEx CERTIFICATION CODE
: Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb
cCSAus CERTIFICATION No
: 1310517X
CSA us CERTIFICATION CODE*
: Class II Div 2, Groups E,F and G, Class III,
Class I Zone 1 AEx e II, Class I Zone 2 AEx nR II, Enclosure Type 4X
c CSA CERTIFICATION CODE
: Class I, Div 2, Groups A,B,C and D, Class II Div 2, Groups E,F and G, Class III,
Ex d IIC, Ex e II, Ex nR II, Enclosure Type 4X
*E** can be used in Class 1, Division 2 Locations for non-explosionproof applications in accordance with Article 501 of the NEC Code
Outer Seal Tightening Guide
GLAND SIZE
25
32
40
50S
50
63S
CABLE DIAMETER
26.2
33.9
25.4
32.9
40.4
46.7
52.8
59.2
24.6
31.9
39.0
45.4
51.4
57.7
23.8
30.8
37.6
44.1
50.0
56.2
23.0
29.8
36.2
42.9
48.7
54.7
22.2
28.8
34.8
41.6
47.3
53.2
21.4
27.8
33.5
40.3
45.9
51.6
20.6
26.8
32.1
39.0
44.5
50.1
19.8
25.7
30.7
37.8
43.2
48.6
19.0
24.7
29.3
36.5
41.8
47.1
18.2
23.7
27.9
35.2
40.4
45.6
Armour Range †
Overall
Across
Across
Cable
Grooved
Stepped
Flats
Corners
Diameter
Protrusion
Cone (X)
Cone (W)
Length
Min
Max
Min
Max Min Max
Max
Max
Size
8.6
6.1
13.1
0.3
1.0
0.8
1.25
24.0
26.4
72.5
20S16
9.5
15.9
0.3
1.0
0.8
1.25
24.0
26.4
70.0
20S
12.5
20.9
0.4
1.0
0.8
1.25
30.5
33.6
73.0
20
14.0
22.0
0.4
1.2
1.25
1.6
37.5
41.3
89.0
25S
18.2
26.2
0.4
1.2
1.25
1.6
37.5
41.3
89.0
25
23.7
33.9
0.4
1.2
1.6
2.0
46.0
50.6
86.0
32
27.9
40.4
0.4
1.6
1.6
2.0
55.0
60.5
90.0
40
35.2
46.7
0.4
1.6
2.0
2.5
60.0
66.0
91.0
50S
40.4
53.0
0.6
1.6
2.0
2.5
70.1
77.1
95.0
50
45.6
59.4
0.6
1.6
2.0
2.5
75.0
82.5
102.0
63S
54.6
65.8
0.6
1.6
2.0
2.5
80.0
88.0
104.0
63
59.0
72.0
0.6
1.6
2.0
2.5
90.0
99.0
115.0
75S
66.7
78.4
0.6
1.6
2.5
3.0
100.0
110.0
117.0
75
76.2
90.3
0.8
1.6
3.15
4.0
114.3
125.4
147.0
90
86.1
101.4
0.8
1.6
3.15
4.0
123.0
135.3
140.0
100
101.5
110.2
0.8
1.6
3.15
4.0
133.4
146.7
162.0
115
110.2
123.2
0.8
1.6
3.15
4.0
152.4
167.6
174.0
130
Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS
Tel: +44 191 265 7411 • Fax: +44 1670 715 646
E-Mail: customerservices@cmp-products.co.uk • Web: www.cmp-products.com
Printed on: 20 February 2018
INSTALLATION INSTRUCTIONS FOR
CMP CABLE GLAND TYPE "E"
FOR TERMINATION OF CABLES WITH WIRE BRAID, TAPE ARMOUR (STA/DSTA), STRIP
ARMOUR & SINGLE WIRE ARMOUR (SWA) (WITH LEAD INNER SHEATH ON "E2"
VARIANT). FOR USE IN EXPLOSIVE ATMOSPHERES.
INCORPORATING EU DECLARATION OF CONFORMITY TO DIRECTIVE [2014/34/EU]
63
75S
75
65.9
72.1
78.5
64.6
70.6
77.2
63.4
69.2
75.9
62.1
67.7
74.6
60.9
66.3
73.3
59.6
64.8
71.9
58.4
63.4
70.6
57.1
61.9
69.3
55.9
60.5
68.0
54.6
59.0
66.7
Combined Ordering
Reference
Cable
(*Brass Metric)
Gland
Shroud
Weight
Ordering
(Kgs)
Type
Suffix
E1FU
1RA
PVC04
0.16
E1FU
1RA
PVC04
0.15
E1FU
1RA
PVC06
0.21
E1FU
1RA
PVC09
0.33
E1FU
1RA
PVC09
0.33
E1FU
1RA
PVC11
0.43
E1FU
1RA
PVC15
0.62
E1FU
1RA
PVC18
0.75
E1FU
1RA
PVC21
0.95
E1FU
1RA
PVC23
1.34
E1FU
1RA
PVC25
1.34
E1FU
1RA
PVC28
2.11
E1FU
1RA
PVC30
2.42
E1FW -
SWA AWA
E1FU
1RA
PVC32
4.21
E1FU
1RA
LSF33
4.45
E2FW -
SWA AWA for lead
E1FU
1RA
LSF34
6.19
E1FU
1RA
LSF35
8.34
sheathed cable
E1FX -
Braid, Tape, etc Armour
E2FX -
Braid, Tape, etc Armour for
lead sheathed cable
E1FU -
Universal Gland for all
Armour Types
E2FU -
Universal Gland for all
Armour Types with lead
sheathed cable
SCAN FOR INSTALLATION VIDEOS
CABLE GLAND TYPES
E1FW, E2FW, E1FX,
E2FX, E1FU & E2FU
Logos shown for illustration purposes only. Please check certification for details