In general
When configuring the DRST-UR, you will be guided through all parameters and you can choose the settings which fit
the application. For each menu there is a scrolling help text which is automatically shown in line 3 on the display.
Configuration is carried out by use of the 3 function keys:
will increase the numerical value or choose the next parameter
will decrease the numerical value or choose the previous parameter
will accept the chosen value and proceed to the next menu
OK
When configuration is completed, the display will return to the default state 1.0.
Pressing and holding
will return to the previous menu or return to the default state (1.0) without saving the changed
OK
values or parameters.
If no key is activated for 1 minute, the display will return to the default state (1.0) without saving the changed values or
parameters.
Further explanations
Fast setpoint adjustment and relay test: These menus allow you to make a quick setpoint change and relay test when
the FastSet menu is activated. This function can only be activated when the relays are set for setpoint function and are
controlled by a setpoint.
Pressing
and
simultaneously will activate a relay test and change the state of the relay.
Pressing
will save the setpoint change.
OK
Holding down
for more than 1 second will return the unit to the default state without saving the setpoint change.
OK
Password protection: Programming access can be blocked by assigning a password. The password is saved in the
transmitter in order to ensure a high degree of protection against unauthorised modifications to the configuration.
Default password 2008 allows access to all configuration menus.