Specifications; Technical Data Fdsb221 - Siemens FDSB221 Technical Manual

Sounder interbase, sounder beacon interbase
Hide thumbs Also See for FDSB221:
Table of Contents

Advertisement

8 Specifications

8.1
Detector line
Line separator
Function
Building Technologies
Fire Safety

Technical data FDSB221

Operating voltage
Operating current:
Standby
Sound activated
Quiescent current connection factor
Address connection factor
Separator connector factor
Protocol
System compatibility
Connection factor: Sound activated
Line voltage:
Nominal
Minimum
Maximum
Voltage at which the separator opens:
Minimum
Maximum
Permanent current when switches are closed:
Switching current (e.g. in the event of a short-circuit)
Leakage current when switches are open:
Serial impedance when switches are closed:
Point detector not used
Point detector used
Number of selectable tones
Number of programmable activation levels
Number of programmable sound levels
1 alarm sound level according to EN 54-3
2 test sound levels
Adjustable maximum sound levels (typical values in
dBA/m at DC 32 V with cover plate FDBZ296)
For details, see 'Annex technical data'
Specifications
Technical data FDSB221
DC 12...33 V
250 μA
3,5 mA
1
1
1
FDnet
See 'List of compatibility'
15
DC 32 V (= V
)
nom
DC 12 V (= V
)
min
DC 33 V (= V
)
max
DC 7.5 V (= V
)
SO min
DC 10.5 V (= V
)
SO max
Max. 0.5 A (= I
)
C max
Max. 1 A (= I
)
S max
Max. 1 mA (= I
)
L max
0.5 Ω (= Z
)
C max
2x 0.5 Ω
11
2
3
77...83 dBA
A6V10320090_c_en_--
02.11.2011
8
31

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fdsb229

Table of Contents