Planning
4

Limitations

4.4
4.5
4.5.1
No.
Tone
Frequency pattern
Sweep from → to
1
Continuous
970 Hz
2
Intermittent
950 Hz
3
Sweep-down
1200 Hz → 500 Hz
4
Slow-whoop
500 Hz → 1200 Hz
Sweep-up,
linear
5
Pulse tone
500 Hz
6
Intermittent
500 Hz
7
Continuous
500 Hz
8
Alternating
560 Hz
440 Hz
9
Intermittent
420 Hz
22
Building Technologies
Fire Safety
Limitations
In the case of the FDSB229 the optical signals and alarm sounds cannot be
synchronized.

Configuration

The following chapters contain the specifications of the different acoustic and
optical signals.
The optical signals are only available with the sounder beacon interbase FDSB229.

Acoustic signals

Pulse pattern
Adjustable max. sound
Norm
levels with cover plate
(typ. values in
[dBA/1m]
)
1
at 12 V
at 32 V
80
83
'evacuate'
BS 5839 Part 1 1988
79
82
'alert'
BS 5839 Part 1 1988
80
82
DIN tone
DIN 33404 Part 3
80
83
NEN 2575
(Netherlands)
76
78
Swedish Standard
SS 03 17 11, No. 1
'Imminent Danger'
75
77
Swedish Standard
SS 03 17 11, No. 6
'Local Warning'
77
79
Swedish Standard
SS 03 17 11, No. 4
'All clear'
77
79
'French fire sound'
NF S 32-001-1975
76
78
Australia 'Alert'
AS 2220 -1978
A6V10320090_c_en_--