8.2
Detector line
Line separator
Function
Building Technologies
Fire Safety

Technical data FDSB229

Operating voltage
Operating current:
Standby
Sound activated
Light activated (luminous intensity
low/medium/high)
Sound and light activated (luminous intensity
low/medium/high)
Quiescent current connection factor
Address connection factor
Separator connector factor
Protocol
System compatibility
Connection factor:
Sound activated
Light activated (luminous intensity
low/medium/high)
Sound and light activated (luminous intensity
low/medium/high)
Line voltage:
Nominal
Minimum
Maximum
Voltage at which the separator opens:
Minimum
Maximum
Permanent current when switches are closed:
Switching current (e.g. in the event of a short-circuit)
Leakage current when switches are open:
Serial impedance when switches are closed:
Point detector not used
Point detector used
Number of selectable tones
Number of programmable activation levels
Number of programmable sound levels
1 alarm sound level according to EN 54-3
2 test sound levels
Adjustable maximum sound levels (typical values in
dBA/m at DC 32 V with cover plate FDBZ296)
For details, see 'Annex technical data'
Specifications
Technical data FDSB229
DC 12...33 V
250 μA
3,5 mA
1.5/4.0/6.5 mA
5.0/7.5/10.5 mA
1
1
1
FDnet
See 'List of compatibility'
15
6/16/26
21/31/41
DC 32 V (= V
)
nom
DC 12 V (= V
)
min
DC 33 V (= V
)
max
DC 7.5 V (= V
)
SO min
DC 10.5 V (= V
)
SO max
Max. 0.5 A (= I
)
C max
Max. 1 A (= I
)
S max
Max. 1 mA (= I
)
L max
0.5 Ω (= Z
)
C max
2x 0.5 Ω
11
2
3
77...83 dBA
A6V10320090_c_en_--
02.11.2011
8
33