Specifications
8
Technical data FDSB229
Ambient conditions
Mechanical data
Standards
34
Building Technologies
Fire Safety
Number of flashing patterns
Number of programmable luminous intensity levels
(not available with all control panels)
Adjustable maximum luminous intensity (typical values
at DC 32 V with cover plate FDBZ296)
For details, see 'Annex technical data'
Operating temperature
Storage temperature
Air humidity
Protection category according to
EN 60529 / IEC 60529:
With point detector fitted
With cover plate FDBZ296 fitted
Electromagnetic compatibility at:
1 MHz...1 GHz
1 GHz...2 GHz
Dimensions (Ø x H)
Weight of FDSB229
Weight of FDBZ296
Material
Color:
Outside
Body
Standards
VdS approvals:
LPCB approvals:
FM approvals:
Certificates:
CE conformity mark
Protection categories
QA Standards
2
3
0.90...3.2 cd
-25...+65 °C
-30...+75 °C
≤ 95 % rel.
IP21C
IP21C
50 V/m
30 V/m
121.8 x 45.2 mm
195 g
31 g
Polycarbonate (PC)
Translucent
∼RAL 9010 pure white
EN 54-3, type A
EN 54-17
G211082
-
-
0786-CPD-21099
Yes
IEC 60529
Siemens Standard
SN 36350
ISO 9001
ISO 9004
A6V10320090_c_en_--
02.11.2011