HSC940 controller's rear as following:
Description of terminal connection:
No.
Function
1
B-
2
B+
3
EM. Stop
4
Fuel
5
Crank
6
Aux. Output 1
7
Aux. Output 2
8
Aux. Output 3
9
Aux. Output 4
12

Wiring Connections

Cable Size
2.5mm
Connected with negative of starter battery
2
Connected with positive of starter battery. Max. 20A fuse is
2.5mm
2
recommended.
1.5mm
Connected with B+ via emergency stop button
2
1.0mm
Fuel relay output; B+ is supplied by 3 terminal; rated 5A
2
Start relay output; B+ is supplied by 3 terminal; rated 5A;
1.0mm
2
Connected to starter coil.
1.0mm
B+ is supplied by 2 terminal; rated 5A
2
1.0mm
B+ is supplied by 2 terminal; rated 5A;
2
1.0mm
B+ is supplied by 2 terminal; rated 5A;
2
1.0mm
B+ is supplied by 2 terminal; rated 5A;
2
Remarks
032-5094-1A-EN