Remote Operation - Siemens RAV12 series User Manual

Self-learning room temperature controller
Table of Contents

Advertisement

Calibration of detector

Remote operation

Siemens Building Technologies
Landis & Staefa Division
Temp.
Offset
DIP-Switch
Reset
If the measured room temperature does not agree with the temperature set on the knob,
the temperature detector can be recalibrated.
This can be done by adjusting a potentiometer that is located on the rear of the unit.
First, the unit must be removed from the socket.
The possible settings on the potentiometer are:
20
15
25
10
30
5
(°C)
(°C)
22.00
20.00
21.75
20.00
21.50
20.00
21.25
20.00
21.00
20.00
20.75
20.00
20.50
20.00
20.25
20.00
20.00
20.00
19.75
20.00
19.50
20.00
19.25
20.00
19.00
20.00
18.75
20.00
18.50
20.00
18.25
20.00
After the corrections are made, the new setting must be confirmed by pressing the reset
button. Otherwise the previous settings are still active! After the reset the controller
can be remounted to the socket.
With the help of a suitable remote operation unit, the controller can be switched to the
economy temperature set for operating mode
making of a potential-free contact connected to terminals T1 and T2.
The LED indicates this by being light.
After the contact opens, the selected operating mode becomes active again.
Operation according to the settings made
on the controller
T1
T2
Suitable remote operation units are e.g.:
– Telephone modem
– manual switch
– window switch
– presence detector
– central unit
Pos.
8
7
6
5
4
3
2
1
0
<= Factory setting
F
E
D
C
B
A
9
. Changeover takes place through the
Continuous economy temperature
T1
T2
2226Z05
CE1N2226E / 01.02.2000
3/8