Rheem RJNL-A036CK Installation Instructions Manual page 28

Rjnl series; rjpl series package heat pumps
Table of Contents

Advertisement

GENERAL DATA - RJNL MODELS
NOMINAL SIZES 3-5 TONS [10.6-17.6 kW]
Model RJNL - Series
Gross Cooling Capacity Btu [kW]
Cooling performance
1
EER, SEER
2
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
High Temp. Btuh [kW] Rating
Heating Performance (Heat Pumps)
System Power KW / COP
Low Temp. Btuh [kW] Rating
System Power KW / COP
HSPF (Btu/Watts-hr)
No/Type
Compressor
Outdoor Sound Rating (dB)
5
Tube Type
Outdoor Coil - Fin Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Tube Type
Indoor Coil - Fin Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
No. Used/Diameter in. [mm]
Outdoor Fan - Type
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
No. Used/Diameter in. [mm]
Indoor Fan - Type
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Furnished
Filter - Type
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Net Weight lbs. [kg]
Weights
Ship Weight lbs. [kg]
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capaci-
NOTES:
ty is net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Outdoor Sound Rating shown is tested in accordance with AHRI Standard
28
A060DK
A060DL
61,000 [17.87]
61,500 [18.02]
11.5/13
11.5/13
2000/2000 [944/944]
2000/2000 [944/944]
59,000 [17.29]
59,000 [17.29]
44,050 [12.91]
44,050 [12.91]
14,950 [4.38]
14,950 [4.38]
5.04
5.04
60,000 [17.58]
60,000 [17.58]
4.78/3.6
4.78/3.6
35,800 [10.49]
35,800 [10.49]
4.31/2.4
4.31/2.4
7.7
7.7
1/Copeland Scroll
1/Copeland Scroll
83
83
Louvered
Louvered
Rifled
Rifled
0.375 [9.5]
0.375 [9.5]
16.56 [1.54]
16.56 [1.54]
2 / 22 [9]
2 / 22 [9]
TX Valves
TX Valves
Louvered
Louvered
Rifled
Rifled
0.375 [9.5]
0.375 [9.5]
5.16
5.16
4 / 13 [5]
4 / 13 [5]
TX Valves
TX Valves
1/0.75 [19.5]
1/0.75 [19.5]
Propeller
Propeller
1/24 [609.6]
1/24 [609.6]
Direct/1
Direct/1
4000 [1888]
4000 [1888]
1 at 1/3 HP
1 at 1/3 HP
1075
1075
FC Centrifugal
FC Centrifugal
1/10x10 [254x254]
1/10x10 [254x254]
Belt/Variable
Belt/Variable
1
1
3/4
1
1725
1725
56
56
Disposable
Disposable
Yes
Yes
(2)1x25x16 [25x635x406]
(2)1x25x16 [25x635x406]
195 [5528]
195 [5528]
565 [256]
565 [256]
580 [263]
580 [263]
270.utdoor Sound Rating shown is tested in accordance with ARI Standard 270.
A060DM
A060JK
Continued ->
61,500 [18.02]
61,000 [17.87]
11.5/13
11.5/13
2000/2000 [944/944]
2000/2000 [944/944]
59,000 [17.29]
59,000 [17.29]
44,050 [12.91]
44,050 [12.91]
14,950 [4.38]
14,950 [4.38]
5.04
5.04
60,000 [17.58]
60,000 [17.58]
4.78/3.6
4.78/3.6
35,800 [10.49]
35,800 [10.49]
4.31/2.4
4.31/2.4
7.7
7.7
1/Copeland Scroll
1/Copeland Scroll
83
83
Louvered
Louvered
Rifled
Rifled
0.375 [9.5]
0.375 [9.5]
16.56 [1.54]
16.56 [1.54]
2 / 22 [9]
2 / 22 [9]
TX Valves
TX Valves
Louvered
Louvered
Rifled
Rifled
0.375 [9.5]
0.375 [9.5]
5.16
5.16
4 / 13 [5]
4 / 13 [5]
TX Valves
TX Valves
1/0.75 [19.5]
1/0.75 [19.5]
Propeller
Propeller
1/24 [609.6]
1/24 [609.6]
Direct/1
Direct/1
4000 [1888]
4000 [1888]
1 at 1/3 HP
1 at 1/3 HP
1075
1075
FC Centrifugal
FC Centrifugal
1/11x9 [279x229]
1/11x9 [279x229]
Direct/2
Direct/2
1
1
1
1
1100
1100
48
48
Disposable
Disposable
Yes
Yes
(2)1x25x16 [25x635x406]
(2)1x25x16 [25x635x406]
195 [5528]
195 [5528]
565 [256]
565 [256]
580 [263]
580 [263]