The connection area must point downward.
Never mount the device with a forward tilt...
Never install the device with a sideways tilt.
Do not mount horizontally...
Mount at eye level to allow operating states to be read at all times.
The ambient temperature should be below 40° C to ensure optimum operation.
Do not expose the inverter to direct sunlight as this can cause excessive
heating and thus power reduction.
In living areas, do not mount the unit on plasterboard walls or similar to avoid
audible vibrations. When in use, the inverter emits noises which may be
perceived as a nuisance in a living area.
Observe the following minimum clearances to walls, other devices or objects
to guarantee sufficient heat dissipation and enough space for pulling the
Electronic Solar Switch handle
Direction
Sides
Above
Below
Front
.
Minimum clearance
300 mm
300 mm
500 mm
50 mm