Page 1
162 205 35-1 29/06/2018 Providing sustainable energy solutions worldwide Installation and Maintenance Manual CTC EcoAir 610M / 614M / 622M Modulating air-to-water heat pump 400 V 3N~ IMPORTANT READ CAREFULLY BEFORE USE AND SAVE FOR FUTURE REFERENCE...
Information in this type of box [!] is particularly important for correctly installing and using the product. Enertech AB provides the information with reservation for any typing errors and subject to modification. CTC EcoAir 610M / 614M / 622M 400V 3N~...
Page 7
CTC EcoZenith i250 / i350 and CTC EcoVent i350F, and are available as accessories for CTC EcoZenith i550 Pro and CTC EcoLogic. Energy labeling decals can be downloaded at www.ctc-heating.com/Ecodesign. CTC EcoAir 610M / 614M / 622M 400V 3N~...
Check and filling, heating system Information on fine adjustments Alarm information Functional test of safety valves fitted Information on procedures for fault registration ______________________________________ ______________________________________ Date / Customer Date / Installer CTC EcoAir 610M / 614M / 622M 400V 3N~...
26/27 dB(A) EcoAir 622M 55/55 dB(A) 36/36 dB(A) 30/30 dB(A) The stated sound values should be considered an indication only, as the level is affected both by power output and the surroundings. CTC EcoAir 610M / 614M / 622M 400V 3N~...
Operating range The control system for CTC EcoAir 600 monitors and ensures that the product functions within its operating range. Primary flow Cº min start temperature (-18 °C) Outside temp. °C CTC EcoAir 610M / 614M / 622M 400V 3N~...
• The installation engineer advises the property owner on the construction and servicing of the system. • The installation engineer fills in a checklist and contact information – the customer and installation engineer sign the list, which the customer keeps. CTC EcoAir 610M / 614M / 622M 400V 3N~...
• If the product is placed in an area where it will be subjected to particularly harsh weather conditions, the product can be installed underneath a small awning. >0.25 m (EcoAir 610M / 614M) >0.4 m (EcoAir 622M) >1 m >0.4 m >2 m CTC EcoAir 610M / 614M / 622M 400V 3N~...
• Place crushed stones around the blocks to achieve optimal drainage. *c.t.c distance – length Moisture barrier, moisture protection mat *distance - depth must be angled away Concrete blocks from the house. Coarse crushed stone approx. 70–100 cm deep. CTC EcoAir 610M / 614M / 622M 400V 3N~...
• The condensation water can also be conducted to the building’s drainage, e.g. downpipe drains. Here a heating cable must be placed in the pipes that are not frost-free. Water trap Frost-free depth CTC EcoAir 610M / 614M / 622M 400V 3N~...
• The product can be bled via the bleed valve inside the condenser. OBS! Only bleed this valve. Other valves are for the cooling system! If these are opened, refrigerant may leak out! CTC EcoAir 610M / 614M / 622M 400V 3N~...
The product used for control monitors and ensures that the heat pump works within its operating range. Speed setting The speed for the circulation pump is set in the Installer/Settings/Heat pump menu. CTC EcoAir 610M / 614M / 622M 400V 3N~...
The compressor heater is pre-connected on delivery. Heat pump connections When installing a heat pump, make sure DIP switch 2 is in the ON position on the heat pump (factory default). CTC EcoAir 610M / 614M / 622M 400V 3N~...
Make sure DIP switch 2 is in the ON position on the last heat pump in the series connection. CTC EcoLogic The last heat pump connected in series must be set to the ON position. CTC EcoAir 610M / 614M / 622M 400V 3N~...
Page 26
Make sure DIP switch 2 is in the ON position on the last heat pump in the series connection. The jumper (PE) must be left in place. CTC EcoAir 610M / 614M / 622M 400V 3N~...
CTC EcoZenith i550 Pro* and CTC EcoLogic can control several heat pumps. CTC EcoLogic *CTC EcoZenith i550 Pro does not control CTC EcoAir 610M CTC EcoZenith i550 Pro (CTC EcoAir 614M/622M All heat pumps are supplied as A1. CTC EcoAir 610M / 614M / 622M 400V 3N~...
1 A 250 V AC. A cable approved for 230 V AC must be used for connecting this output, irrespective of the load that is connected. For connection information, see the wiring diagram. Close-up from wiring diagram. CTC EcoAir 610M / 614M / 622M 400V 3N~...
The evaporator and outer covering should be cleaned with a damp cloth or soft brush. No other periodic maintenance or inspection is necessary. CTC EcoAir 610M / 614M / 622M 400V 3N~...
Page 37
As an accessory you can buy a heating cable to connect to EcoAir. The cable is fitted in the drain from the condensation tray to the frost-free drain. Condensation tray and drain CTC EcoAir 610M / 614M / 622M 400V 3N~...
If the pump heats poorly, check that no unusual ice formation has occurred. Possible reasons for this: • Defective defrosting automation • Lack of refrigerant (leakage) • Extreme weather conditions. CTC EcoAir 610M / 614M / 622M 400V 3N~...