Wiring

Connect the Galaxy TouchCenter Plus to the panel's RS485 terminals. For maximum wire runs and wire sizes, refer to
your panel's installation manual.
The keypad draws up to 340mA at 9.6VDC, 260mA at 12VDC and 250mA at 13.8VDC.
If you power the keypad from your panel's auxiliary power output, check your panel's Installation and Setup
Guide and verify that this device and others do not exceed your panel's auxiliary power output capability. If it
does, use a supplementary power supply.
Connect the RS485 wires to the keypad terminal block as shown below.