VOYAGEUR GRAND AU
WARNING
Fire Risk.
Comply with all minimum clearances to
combustibles as specified.
Failure to comply may cause house fire.
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having
jurisdiction
2 - 15mm layers of compressed
cement sheets with a thermal
conductivity of 0.5 W/m˚K.
127mm or more from bottom of
unit, ember protection only
Figure 10.1
NOTE: Hearth Rug may be used in Suggested Area.
10
required
Material
Thermal Resistance: R value
The R value is a measure of a material's resistance to heat
transfer.
R value is convenient when more than one material is used
since you can add the R values together, whereas you can
not do this for k value.
The HIGHER the R factor means less heat is being
conducted through the non-combustible material to the
combustible material beneath it.
The R value of a material must be equal or larger then the
required R value to be acceptable.
Quadra-Fire Voyageur Grand ACC does not require a
insulating Floor Protector, as they are tested and comply
with the minimum Floor Protector requirements of AS/
NZS 2918:2001.
NOTE: Heat shield requirements for heat sensitive walls.
Clearances may be reduced by provision of an
appropriately located heat shield refer to AS/NZS
2918:2001 3.2.3.
7075-177A
17 August, 2018