BE SURE POWER IS DISCONNECTED PRIOR TO INSTALLATION!
READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION.
SymCom's PumpSaver
well, dead-head, jammed impeller, rapid-cycling, overvoltage and undervoltage conditions. The
®
PumpSaver
Plus Model 233P protects 230V, 2 or 3-wire, 1/3 to 3 hp pumps. The PumpSaver
Model 233P-1.5 protects 230V, 2 or 3-wire, 1/3 to 1.5 hp pumps. The PumpSaver
protects 115V, 2 or 3-wire, 1/3 to 1 hp pumps. Typical applications include submersible pumps,
centrifugal pumps, circulating pumps, cooling pumps, environmental pumps, residential waterwells,
commercial waterwells, irrigation wells, and golf course and other sprinkler systems.
CONNECTIONS
NOTE: Use with UL/CSA listed overload or impedance protected pumps or motors only.
1.
Mount the PumpSaver
location is wet or dusty a NEMA 3R, 4, or 12 enclosure should be used. The PumpSaver
must be protected by a fuse or circuit breaker (30A RK5 fuse or 30A inverse time breaker max).
2.
Connect one line from the fused disconnect to the L1 IN terminal of the PumpSaver
a wire from the L1 OUT terminal to the other in-line controls such as pressure or float switches.
3.
Connect the other line from the fused disconnect (ungrounded fused conductor) to the L2 IN
terminal of the PumpSaver
controls such as pressure or float switches (see Figure 1).
4.
Refer to the appropriate wiring diagram for your specific application:
• Typical wiring diagram
• Standard 3-wire control box
• Deluxe control box
• 2-Wire pump direct feed
PROPER OPERATION REQUIRES FIELD CALIBRATION
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
FOLLOW NATIONAL, STATE AND LOCAL CODES.
®
Plus is a pump monitor designed to protect single-phase pumps from dry-
®
Plus in a convenient location in or near the pump control box. If the
®
Plus. Run a wire from the L2 OUT terminal to the other in-line
– Figure 1
– Figure 2
– Figure 3
– Figure 4
*** WARNING ***
®
Plus
®
Plus Model 111P
®
Plus
®
Plus. Run
Need help?
Do you have a question about the PumpSaver Plus 111P and is the answer not in the manual?
Questions and answers