Haier AB25S2SC1FA Service Manual page 137

R32
Table of Contents

Advertisement

MULTI:
D: Entering condition
When the compressor running frequency is lower than 58Hz (E) continuously for 8 hrs, the system
will enter oil return operation. In the course of mode changeover, manual unit stop or protective
unit stop, the time will be accumulative. After the compressor restarts up, the time will be counted
continuously. In a continuous 8 hrs, if the compressor running frequency is not less than 72Hz for
over 10 minutes continuously, the accumulative time will be cleared. Also after the heating
defrosting, the time will be cleared.
E: Procedure
Cooling mode: refer to "the oil return procedure in cooling mode"
Heating mode: refer to "the oil return procedure in heating mode"
F: The protection treatment in oil return operation
In the course of oil return, because of protection or abnormal unit stop, after the unit restarts up,
the time will not be cleared, the system will need another oil return operation. In the refrigerant
flow course in the oil return of cooling mode or after the oil return, and within 5 minutes after the
refrigerant being eliminated is over, the anti-freezed protection is invalid, and also the low voltage
protection is invalid. But the other protection is valid.
In the course of oil return from heating mode to cooling mode, if abnormal condition occurs or the
unit stops for protection, then the system needs not another oil return within 3 minutes after the
unit stops and it will start up directly, then to heating mode.
In the course of oil return from heating mode to cooling mode, the anti-freezed protection is null
and void, and the low voltage protection is null either. The other protection is valid.
Oil return procedure in cooling mode:
Send oil return signal
Inverter compressor
running indoor PMV
stopped indoor PMV
Outdoor motor
running indoor motor AUTO
stopped indoor motor STOP
4-way valve
oil return begins
60s
Oil return frequency
auto frequency
auto angle
OFF angle 5(E)
AUTO
AUTO (TC or ambient temp. control)
AUTO (set fan speed)
OFF
135
oil return over
ref. eliminated
Low frequency
350pulse(E)
120pulse(E)
80(E)
OFF angle 5(E)
STOP
OFF
30s
auto frequency
auto angle
AUTO
AUTO
STOP
OFF

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents