Quit condition of oil return:
OR
Max. 10 minutes
Oil return procedure in heating mode:
Send oil return signal
Inverter compressor indicated FQY
outdoor motor
auto
4-way valve
PMV auto open angel
all indoor motor ON
OFF
Quit condition of oil return
Max. 9 minutes(E)
OR
1 minute later after oil return is over
Td‐Tcm>30℃
OR
Ts‐Tc>30℃
Tc<‐35℃
oil return beginning
60s
oil return frequency
0HZ
5s
auto(TC control)
ON
OFF
450pulse
300pulse (E)
OR
Td‐Tcm<20℃ for 30s(5 minutes later, begin to count)
T s ‐Tc<15℃ for 30 S(5 minutes later, begin to count)
Running for min. 5 minutes(E)
134
oil return over
120s
Soft startup
0HZ
auto
15s
450 pulse
auto open angle
anti-freeze startup