Technical Data - ABB PST30 Installation And Maintenance Manual

Pst series; pstb series
Hide thumbs Also See for PST30:
Table of Contents

Advertisement

3:8 Technical data

3:8.1 General
Item
Rated insulation voltage, Ui
Rated operational voltage, Ue
Rated control voltage, Us
Rated frequency
Voltage tolerances
Frequency tolerances
Rated impulse withstand voltage
Number of controlled phases
Programmable inputs
Output relays
Battery back-up D20mm
PTC input
Cooling system
Recommended fuse for control circuit
Service factor
Communication protocols
3:8.2 Semi-conductor fuses
Softstarter type
A
PST30
80
PST37
125
PST44
160
PST50
160
PST60
200
PST72
250
PST85
315
PST105
400
PST142
450
PST175
500
PST210
630
PST250
700
PST300
900
PSTB370
700
Low Voltage Products & Systems
ABB nc. • 888-385-1221 • www.abb-control.com
Chapter 3 - Description
Technical data
690V
208-690 V (in two modes)
100 - 250 V 50/60 Hz
50 / 60 Hz
+10% to -15%
±5%
2 kV
3
24 VDC, 10 mA
250 VAC, Ith = 5A, le = 1.5A (AC-15)
Lithium 3V CR2032
2825 ohm ±20% switch off resistance
1200 ohm ±20% switch on resistance
Fan
6A Delayed
MCB use C characteristics
115% (100% for PSTB1050)
AS-Interface DeviceNet / Profibus DP /
Modbus
Bussmann fuses
Holders
Type
170M1366
170H1007
170M1368
170H1007
170M1369
170H1007
170M1369
170H1007
170M1370
170H1007
170M1371
170H1007
170M1372
170H1007
170M3019
170H3004
170M3020
170H3004
170M3021
170H3004
170M5012
170H3004
170M5013
170H3004
170M5015
170H3004
170M5013
170H3004
3
3.5
1SXU 132 021 M0201