Setup Mode; Automatic Turning Mode; Product Information Mode; Operator Mode - Honeywell UDC1200 MICRO-PRO Product Manual

Universal digital controller
Hide thumbs Also See for UDC1200 MICRO-PRO:

Advertisement

Code
Input Type & Range
Code
Input Type & Range
B: 100 – 1824 ºC
L: 0.0 – 537.7 ºC
bC
L.C
B: 211 – 3315 ºF
L: 32.0 – 999.9 ºF
L.F
bF
C: 0 – 2320 ºC
N: 0 – 1399 ºC
CC
NC
C: 32 – 4208 ºF
N: 32 – 2551 ºF
CF
NF
J: -200 – 1200 ºC
R: 0 – 1759 ºC
JC
rC
J: -328 – 2192 ºF
R: 32 – 3198 ºF
JF
rF
J: -128.8 – 537.7 ºC
S: 0 – 1762 ºC
j.C
SC
J: -199.9 – 999.9 ºF
S: 32 – 3204 ºF
j.F
SF
K: -240 – 1373 ºC
T: -240 – 400 ºC
KC
tC
K: -400 – 2503 ºF
T: -400 – 752 ºF
KF
tF
K: -128.8 – 537.7 ºC
T: -128.8 – 400.0 ºC
k.C
t.C
K: -199.9 – 999.9 ºF
T: -199.9 – 752.0 ºF
K.F
t.F
L: 0 – 762 ºC
LC
PtRh20% vs 40%:
P24C
0 – 1850 ºC
L: 32 – 1403 ºF
LF

4. SETUP MODE

Note: Configuration must be completed before adjusting Setup parameters.
First select Setup mode from Select mode (refer to section 2). While in Setup Mode
Press
to scroll through the parameters, then press
To exit from Setup mode, hold down
and press
, to return to Select mode.
Note: Parameters displayed depends on how instrument has been configured.
Parameter
Lower
Upper Display
Display
Adjustment Range
Input Filter Time constant
.0'#%
OFF or 0.5 to 100.0 secs
Process Variable Offset
!..&%
+/- Span of controller
Primary (Heat) power
PPWw
Current power levels (read only)
Secondary (Cool) power
SPWw
3<93%
Primary Proportional Band
0.0% (ON/OFF) and 0.5% to
999.9% of input span.
3<9&%
Secondary Proportional Band
Automatic Reset (Integral Time)
1$?#%
1 sec to 99 mins 59 secs and OFF
Rate (Derivative Time)
$16;%
00 secs to 99 mins 59 secs
Overlap/Deadband
!'%
-20 to +20% of Primary and
Secondary Proportional Band
Manual Reset (Bias)
<01&%
0%(-100% if dual control) to 100%
Primary ON/OFF Differential
40.3%
0.1% to 10.0% of input span
Secondary ON/OFF Diff.
40.&%
centered about the setpoint
Prim. & Sec. ON/OFF Diff.
40..%
Setpoint Upper Limit
&32'%
Current Setpoint to Range max
&3''%
Setpoint Lower limit
Range min to Current Setpoint
Primary Output Power Limit
!32'%
0% to 100% of full power.
Output 1 Cycle Time
(6*%
0.5, 1, 2, 4, 8, 16, 32, 64, 128,
Output 2 Cycle Time
(6/%
256 or 512 secs.
Output 3 Cycle Time
(6F%
High Alarm 1 value
3=1*%
Range Min. to Range Max.
3'1*%
Low Alarm 1 value
41'*%
Deviation Alarm 1 Value
+/- Span from SP in display units
Band Alarm 1 value
<1'*%
1 LSD to span from setpoint
Alarm 1 Hysteresis
1:7*%
1 LSD to full span in display units
High Alarm 2 value
3=1/%
Range Min. to Range Max.
Low Alarm 2 value
3'1/%
41'/%
Deviation Alarm 2 Value
+/- Span from SP in display units
<1'/%
Band Alarm 2 value
1 LSD to span from setpoint
Alarm 2 Hysteresis
1:7*%
1 LSD to full span in display units
Loop Alarm Time
'160%
1 sec to 99 mins. 59secs.
Auto Pre-tune
136%
40&1%disabled or
3,;-%
Auto/manual Control selection
;-1< enabled
Setpoint ramping
&"$%
SP Ramp Rate Value
1 to 9999 units/hour or Off (blank)
rP
SP Value
Scale range upper to lower limits
SP
SP1 Value
Scale range upper to lower limits
_ SP1
" _"" indicates currently active SP.
SP2 Value
_ SP2
Setup Lock Code
&',B%
0 to 9999
Code
Input Type & Range
5. AUTOMATIC TUNING MODE
First select Automatic tuning mode from Select mode (refer to section 2).
PtRh20% vs 40%:
P24F
Press
to scroll through the modes, then press
32 – 3362 ºF
To exit from Automatic tuning mode, hold down
Pt100: -199 – 800 ºC
PTC
Pre-tune is a single-shot routine and is thus self-disengaging when complete.
Pt100: -328 – 1472 ºF
PtF
If 136 in Setup mode = ;-1<, Pre-tune will attempt to run at every power up*.
Pt100: -128.8 – 537.7 ºC
Pt.C
Refer to the full user guide (available from your supplier) for details on controller tuning.
Pt100: -199.9 – 999.9 ºF
Pt.F
Parameter
+9/+%
0 – 20 mA DC
4 – 20 mA DC
E9/+%
Pre-Tune
+9>+%
0 – 50 mV DC
*+>+%
10 – 50 mV DC
Self-Tune
+9>%
0 – 5 V DC
Tune Lock
*9>%
1 – 5 V DC
* Note: Automatic tuning will not engage if either proportional band = 0. Also, Pre-tune
+9*+%
0 – 10 V DC
will not engage if setpoint is ramping, or the PV is within 5% of span of the setpoint.
2 – 10 V DC
/9*+%

6. PRODUCT INFORMATION MODE

First select Product information mode from Select mode (refer to section 2).
Press
to view each parameter. To exit from Product Information mode, hold down
is lit.
and press
or
to set the required value.
Parameter
Input type
Default
Option 1 module type
fitted
/.+
+
N/A
Option 2 type fitted
*+.+
Option 3 type fitted
Auxiliary Option module
>.++
type fitted
*.*>
+
Firmware type
/>
Firmware issue
Product Revision Level
+.>
Date of manufacture
Serial number 1
R/max
Serial number 2
R/min
Serial number 3
*++

7. OPERATOR MODE

This mode is entered at power on. It can also be accessed from Select mode (see section 2).
F/
Note: All configuration mode and Setup mode parameters must be set as required
before starting normal operations.
Press
to scroll through the parameters, then press
R/max
Note: All parameters in Display strategy 6 are read only, and can only be adjusted via
R/min
Setup mode.
>
Upper
>
Display
*
PV Value
R/max
PV Value
R/min
>
PV Value
>
Active SP
*
Value
@@.>@
SP Value
SP1 Value
40&1
SP2 Value
Off
Scale
Actual SP
Range
Value
min
Ramp
*+
Rate
or
to set the required value.
and press
to return to Select mode.
Lower
Upper Display
Display
Adjustment Range
3#2-%
On
Off.
OFF
or
Indication remains
if automatic
&#2-%
tuning cannot be used at this time*.
#',B%
0 to 9999
to return to Select mode. Note: These parameters are all read only.
Lower
Upper
Display
Display
A-9*%
D-0%
Universal input only
-,-;%
$'I%
!3-*%
&&$%
#$0%
'0-%
Linear voltage / Current output
!3-/%
!3-F%
-,-)%
!3-1%
$EH>%
4050%
.JK%
Value displayed is firmware type number
A??%
Value displayed is firmware issue number
38'%
Value displayed is Product Revision level.
Manufacturing date code (mmyy)
4!
%
Mm
&-*%
First four digits of serial number
&-/%
Middle four digits of serial number
&-F%
Last four digits of serial number
or
to set the required value.
Lower
Display Strategy
Display
When Visible
Active SP
1 & 2 (initial screen)
PV and target value of selected SP
Value
SP adjustable in Strategy 2
Actual SP
3 & 6 (initial screen)
PV and actual value of selected SP
Value
(e.g. ramping SP value). Read only
(Blank)
4 (initial screen)
Process variable only. Read only
(Blank)
5 (initial screen)
Target value of selected setpoint only.
1, 3, 4, 5 & 6 if digital
SP
input is not 40&*
Adjustable except in Strategy 6
Target value of SP1
"lit if dig I/P = 40&*
_
"
_ SP1
Adjustable except in Strategy 6
and active SP is SP1
Target value of SP2
"lit if dig I/P = 40&*
_
"
_ SP2
Adjustable except in Strategy 6
and active SP is SP2
Actual (ramping) value of selected SP
&"$ enabled and
rP
SPrP
is not zero
&"$ enabled in Setup
SP ramping rate, in units per hour.
rP
Adjustable except in Strategy 6
mode
Upper
Lower
Display
Display
Active
Alarms
&
AL
t
Manual Control
Default
If 3,;- is set to ;-1< in Setup mode, manual control can be selected/de-selected by
pressing the
key while in Operator mode, or by changing the status of the digital input if
4050 has been configured for 401? in Configuration mode. The
Off
while in Manual Control mode and the lower display will show 3xxx (where xxx is the current
manual power level). Switching to/from manual mode is via Bumpless Transfer.
+
to set the required output power. Caution: Not restricted by !32' limit.
Press
or
8. ERROR/FAULT INDICATIONS
Parameter
Upper
Display
Instrument
parameters are in
5,#,%
default conditions
Description
Over Range
::
L
No option fitted.
''
Under Range
L
Relay
Sensor Break
!3;N%
SSR drive
Option 1 Error
Triac
Option 2 Error
;88%
Option 3 Error
Option A Error
As Option 1.
9. SERIAL COMMUNICATIONS
No option fitted
Refer to the full user guide (available from your supplier) for details of this option.
RS485 comms
10. SPECIFICATIONS
Digital Input
UNIVERSAL INPUT
Impedance:
>10MΩ resistive, except DC mA (5Ω) and V (47kΩ ).
Isolation:
Isolated from all outputs (except SSR) at 240VAC.
DIGITAL INPUT
Volt-free(or TTL):
Open(2-24VDC) = SP1 or Auto, Closed(<0.8VDC) = SP2
OUTPUTS
Relay
Contact Type/Rating:
Single pole double throw (SPDT); 2A resistive at 120/240VAC.
Lifetime:
>500,000 operations at rated voltage/current.
Isolation:
Isolated from input and other outputs.
SSR Drive/TTL
Drive Capability:
SSR >10V into 500Ω min.
Isolation:
Not isolated from input or other SSR drive outputs.
Triac
Operating Voltage:
20 - 280Vrms (47 - 63Hz)
Current Rating:
0.01 - 1A (full cycle rms on-state @ 25°C); derates linearly above
40°C to 0.5A @ 80°C.
Isolation:
Isolated from input and other outputs.
Description
DC
Resolution:
8 bits in 250mS (10 bits in 1s typical, >10 bits in >1s typical).
Isolation:
Isolated from input and other outputs.
OPERATING CONDITIONS FOR INDOOR USE
Ambient Temperature: 0°C to 55°C (Operating)
Ambient Temperature: –20°C to 80°C (Storage)
Relative Humidity:
20% - 95% non-condensing
Supply Voltage:
100 - 240VAC 50/60Hz 7.5VA for mains powered versions.
20 - 48VAC 50/60Hz (option) 7.5VA or
Read only
22 - 65VDC 5W maximum for low voltage versions
Target value of SP
ENVIRONMENTAL
Standards:
CE, UL, ULC
EMI:
Complies with EN61326 (Susceptibility & Emissions)
Safety Considerations: Complies with EN61010-1 & UL3121
Pollution Degree 2, Installation Category II
Front Panel Sealing:
To IP66
PHYSICAL
Dimensions Depth:
110mm (behind panel)
Read only
Front panel height:
48mm
Front panel width:
48mm
Weight:
0.21kg maximum
Display Strategy
Description
When Visible
When one or more
L
Alarm 2 active
alarms are active.
L21
Alarm 1 active
ALM indicator
will also flash%
L
Loop Alarm active
indicator will flash
Lower
Description
Display
Configuration & Setup required. Seen at first
turn on or if hardware configuration changed.
(,-.
Press
to enter the Configuration Mode,
next press
or
to enter the unlock
code number, then press
to proceed.
%
Normal
Input > 5% over-range
M
%
Normal
Input > 5% under-range
M
Normal
Break in input sensor or wiring
!"-*%
Option 1 module fault
!"-/%
Option 2 module fault
!"-F%
Option 3 module fault
!"-1
Auxiliary Option module fault