Transport And Handling; By Receiving Inspection; Storage - ABB SafeRing 36 Installation And Operating Instructions Manual

Table of Contents

Advertisement

<90
0


SAFERING 36
6 SafeRing/SafePlus 36kV | Installation and operating instruction
ø30

2. TRANSPORT AND HANDLING

The units are delivered from the factory ready for installation.
Weight table for standard SafeRing
2-way DeF / DeV
550 kg
3-way CCF / CCV
800 kg
4-way CCCF / CCCV
1050 kg
4-way CCFF / CCVV
1100 kg
3-way CCC
750 kg
4-way CCCC
1000kg
SafePlus
Standard 1-way
300 kg
Standard 2-way
600 kg
3 and 4-way as for SafeRing
The weights are including additional equipment.
SafeRing / SafePlus is fitted with lifting lugs, but can also be
moved on pallets with a forklift truck.
The units are top heavy so please handle with care!

2.1 BY RECEIVING INSPECTION

Upon receiving the SafeRing / SafePlus please check that the
delivered equipment has not been damaged during transport.
If any such damage has occurred, a claim must be submitted
to the carrier immediately.
After unpacking, the following must be checked:
1. Operating handle – 1 piece should be included, normally
fixed on right hand side .
2. Check that the pointer on the pressure indicator is in the
green area.
3. Carry out a function test on the mechanical parts.
Any faults or omissions must be reported immediately to the
supplier.

2.2 STORAGE

SafeRing / SafePlus must be stored under cover in a dry and
well ventilated area until it is installed and put into operation.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Safeplus 36

Table of Contents