Prefabricated cable termination.
Cable compartment for C-, D- and De-modules
Adjustable cable
support bar
Cable clamp (additional equipment)
12 SafeRing/SafePlus 36kV | Installation and operating instruction
Earthing bar

4.2 CABLE CONNECTION

SafeRing/ SafePlus is equipped with cable bushings outside
cone type which comply with CENELEC EN 50181 interface B
(400 series plug-in) or interface C (400 series bolted).
All bushings are protected by the cable cover.
Cable terminations
The following types are recommended:
Euromold / Elastimold
Tyco Electronics
nkt-cables
Prysmian
Südkabel
ABB Kabeldon
Please see supplier documentation for details.
The manufacturer's installation instructions must be followed.
Be sure to lubricate the bushings thoroughly with the silicone
supplied.
NOTE!
Where cables are not connected, the earthing switch must be
locked in closed position or the bushings must be fitted with-
dead end receptacles before the unit is put into operation.
Cable compartment V-module with mounting plate for current
transformers and fixed cable support bar