3. TECHNICAL DATA

3.1 ELECTRICAL DATA

SafeRing / SafePlus 36
Rated voltage
Power frequency withstand voltage
- across disconnector
Lightning impulse withstand voltage
- across disconnector
Rated normal current
Breaking capacities:
- active load
- closed loop
- off load cable charging
- earth fault
- earth fault cable charging
- transfer current
- short-circuit breaking current
Making capacity
Class (Electrical endurance)
4)
Short time current 1 sec.
Short time current 3 sec.
Internal arc classification IAC AFL, 1s
1)
400A for bushings Interface B (400 series plug-in)
2)
Depending on the current rating of the fuse-link
3)
Limited by high voltage fuse-links
4)
Maximum rating for bushings Interface B (400 series plug-in)
C-module
Switch
Earthing
disconnector
switch
kV
36/38,5/40,5
36/38,5/40,5
kV
70/80/95
70/80/95
kV
80/95/110
kV
170/180/185
170/180/185
kV
195/210/215
A
630/630/630
1)
A
630/630/630
A
630/630/630
A
20/21/21
A
60/63/63
A
35/36/36
A
kA
kA
50/50/50
50/50/50
(5 times)
(5 times)
E3/E2/E2
E2/E2/E2
kA
16/16/16
16/16/16
kA
16/16/16
16/16/16
kA
20/20/20
F-module
Switch-fuse
Downstream
disconnector
earthing
switch
36/38,5/40,5
36/38,5/40,5
70/80/95
70/80/95
80/95/110
170/180/185
170/180/185
195/210/215
200/200/200
2)
200/200/200
200/200/200
20/21/21
60/63/63
35/36/36
840/750/750
see
3)
3)
see
2,5/2,5/2,5
(5 times)
- / -
E2/E2/E2
1/1/1
3)
see
20/20/20
Installation and operating instruction | SafeRing/SafePlus 36kV 7
V-module
Vacuum
Earthing
circuit-
switch/
breaker
disconnetor
36/38,5/40,5
36/38,5/40,5
70/80/95
70/80/95
80/95/110
170/180/185
170/180/185
195/210/215
630/630/630
1)
50/50/50
(Class C1)
20/20/20
(Class E1,S1)
50/50/50
50/50/50
E1/E1/E1
E2/E2/E2
16/16/16
16/16/16
16/16/16
16/16/16
20/20/20