Figure 19; Th-Tune Setup Options Using The Tec-Eye; Comfort Range; Alarms And Troubleshooting - Bard W18AAPA Installation Instructions Manual

Multi-tec/th-tune; free cooling unit system; multi-tec wall-mount air conditioner
Table of Contents

Advertisement

FIGURE 19

Change Setpoint

th-Tune Setup Options Using the TEC-EYE

At this time, there is only one th-TUNE option, comfort
range, that can be set up using the TEC-EYE hand-held
diagnostic tool. For additional information about using
the TEC-EYE, see the latest revision of MULTI-TEC
Service Instructions manual 2100-665.

Comfort Range

This value sets the temperature range around the
setpoint where the unit will not heat or cool.
Example: If the comfort range is set to 5°F and the
setpoint is set to 72°F, heating would occur when room
temperature is below 68.5°F and cooling would occur
when room temperature is above 75.5°F.
To adjust the comfort range using the TEC-EYE:
1. Connect the TEC-EYE diagnostic tool to the control
board located in the wall unit. The TEC-EYE
connects to the control board via an RJ11 modular
phone connector.
The initial screen that will display on the TEC-EYE
is the status screen for the MULTI-TEC wall unit.
If the th-Tune has been properly connected to the
wall unit, the status screen should look like Figure
20.
FIGURE 20

MULTI-TEC Status Screen

2. Press MENU key to go to the Main Menu screen.
3. Press UP or DOWN keys and ENTER key to enter
TECHNICIAN password 1313.
4. Press UP or DOWN keys to scroll to Adv System
Config; press ENTER key.
5. Press UP or DOWN keys to scroll to th_Tune Setup
(B4); press ENTER key.
6. Press ENTER key to scroll to Comfort Range (see
Figure 21).
7. Press UP or DOWN keys to adjust value.
8. Press ENTER key to save.
FIGURE 21

Comfort Range Setup

Alarms and Troubleshooting

Alarms

If any alarm is triggered on the unit, the Bell icon will
flash for 10 seconds accompanied by an audible tone
alarm. After 10 seconds, the bell icon will stop flashing
and become solid and the audible tone alarm will be
silenced. If any alarm is present on the unit, the TEC-
EYE display will need to be used to find out what the
alarm is.

Troubleshooting

The th-Tune device is only a single unit controller.
It provides a means to display basic information
from the MULTI-TEC wall-mount unit and provides a
temperature and humidity probe to better measure a
room's climate. That means that all variables and unit
operation is handled at the wall unit controller, and any
troubleshooting beyond communication loss with the
th-Tune will require the use of the TEC-EYE display.
In the case of a loss of communication between th-
Tune and the wall unit controller, a "Cn" will appear
in the main display area. In that case, check the
communications wiring.
Manual