Dhw Temperature Control - Danfoss Termix BTD RO MIX Operating Manual

Table of Contents

Advertisement

Operating Guide
Termix BTD RO MIX

6.2 DHW temperature control

DHW temperature control
There are various types of DHW temperature control used in
Danfoss substations.
DHW temperature should be adjusted to 45-50 °C, as this provides
optimal utilisation of DH water. At DHW temperatures above 55 °C,
the possibility of lime scale deposits increases significantly.
6.2.1 RAVK controller
RAVK controller (25-65 °C). The temperature setting is as follows:
1 = 25 °C
2 = 35 °C
3 = 45 °C
4 = 55 °C
5 = 65 °C
The values are intended as a guide.
Thermostatic control
DHW temperature is adjusted as follows:
To increase temperature, turn the handle on the thermostatic
controller to select a higher number.
To decrease temperature, turn the handle on the thermostatic
controller to select a lower number.
6.2.2 AVTB controller (20–60 °)
The temperature setting is as follows:
1 = 20 °C
2 = 35 °C
3 = 50 °C
4 = 60 °C
5 = 70 °C
The values are intended as a guide.
The AVTB operates at its best at DH supply temperatures of up to
90 °C.
Thermostatic control
DHW temperature is adjusted as follows:
To increase temperature, turn the handle on the thermostatic
controller to select a higher number.
To decrease temperature, turn the handle on the thermostatic
controller to select a lower number.
Danfoss District Energy
VI.HE.F2.02 / LUK40661
DEN-GT
13

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Termix BTD RO MIX and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Table of Contents