a.
Attach each of the front- and rear-post brackets to the switch using four of the included
bracket screws.
b.
Use an additional two screws to secure each of the rear-post brackets at the midpoint on the
sides of the switch.
c.
Use the screws and cage nuts supplied with the rack to secure the switch in the rack.
Step 3.
Adjust the rear-post bracket ears.
a.
Lock the position of the rear-post bracket ears using the included position-locking screws.
You can also adjust the rear-post bracket ears to fit different rack depths from 56 cm to 75 cm.
Step 4.
Ground the switch.
a.
Ensure the rack is properly grounded and in compliance with ETSI ETS 300 253. Verify that
there is a good electrical connection to the grounding point on the rack (no paint or isolating
surface treatment).
b.
Attach the grounding wire #14 AWG to the grounding point on the switch rear panel. Then
connect the other end of the wire to the rack ground.
CAUTION:
The earth connection must not be removed unless all supply connections have been
disconnected.
22
Lenovo ThinkAgile CP Hardware Installation Guide