System Charge; Heat Pump Flow Diagram - York YZE SERIES Installation Manual

Outdoor split-system heat pump
Table of Contents

Advertisement

SECTION VI: EVACUATION
It will be necessary to evacuate the system to 500 microns or less. If a
leak is suspected, leak test with dry nitrogen to locate the leak. Repair
the leak and test again.
To verify that the system has no leaks, simply close the valve to the vac-
uum pump suction to isolate the pump and hold the system under vac-
uum. Watch the micron gauge for a few minutes. If the micron gauge
indicates a steady and continuous rise, it's an indication of a leak. If the
gauge shows a rise, then levels off after a few minutes and remains
fairly constant, its an indication that the system is leak free but still con-
tains moisture and may require further evacuation if the reading is
above 500 microns.
SECTION VII: SYSTEM CHARGE
R-410A refrigerant cylinders are rose colored, and have a dip tube
which allows liquid to flow out of the cylinder in the
tion.
Always charge the system slowly with the tank in the upright
position.
The factory charge in the outdoor unit includes enough charge for the
unit, a 15 ft. line set and the smallest indoor coil match-up. Some indoor
coil matches may require additional charge. See tabular data sheet pro-
vided in unit literature packet for charge requirements.
Do not leave the system open to the atmosphere. Unit damage
could occur due to moisture being absorbed by the POE oil in the
system. This type of oil is highly susceptible to moisture absorp-
tion.
The "TOTAL SYSTEM CHARGE" must be permanently stamped on the
unit data plate.
Total system charge is determined as follows:
1.
Determine outdoor unit charge from tabular data sheet.
2.
Determine indoor coil adjustment from tabular data sheet.
3.
Calculate the line charge using the tabular data sheet if line length
is greater than15 feet.
4.
Total system charge = item 1 + item 2 + item 3.
5.
Permanently stamp the unit data plate with the total amount of
refrigerant in the system.
Use the following subcooling charging method whenever additional
refrigerant is required for the system charge. A superheat charging
method is not suitable for TXV equipped systems.
FIGURE 10: Heat Pump Flow Diagram
Unitary Products Group
Upright Posi-
OUTDOOR
COIL
SUCTION
ACCUMULATOR
LIQUID
SENSOR
COOLING CYCLE FLOW
HEATING CYCLE FLOW
Refrigerant charging should only be carried out by a qualified air
conditioning contractor.
Measurement Method
If a calibrated charging cylinder or accurate weighing device is avail-
able, add refrigerant accordingly.
Compressor damage will occur if system is improperly charged. On
new system installations, charge system per tabular data sheet for
the matched coil and follow guidelines in this instruction.
Check flare caps on service ports to be sure they are leak tight. DO
NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum).
Subcooling Charging Method
For the heating operation, there is no accurate subcooling method for
charging the unit. If unit charging is required during heating operation,
the unit must be evacuated and charge weighed-in per the marking on
the rating plate.
For the cooling operation, the recommended subcooling is typically
around 10°F. This may vary greatly based on each unique syatem.
1.
Set the system running in the cooling mode by setting the thermo-
stat at least 6°F below the room temperature.
2.
Operate the system for a minimum of 15-20 minutes.
3.
Refer to the tabular data sheet for the recommended airflow and
verify this indoor airflow (it should be about 400 SCFM per ton).
4.
Measure the liquid refrigerant pressure P and temperature T at the
service valve.
5.
Calculate the saturated liquid temperature ST from Table 12 on the
last page of this document.
6.
Subcooling temperature TC = Saturated Temperature (ST) - Liquid
Temp (T).
Example: The pressure P and temperature T measured at the liquid
service port is 360 Psig and 93°F. From Table 12, the saturated tem-
perature for 360 Psig is 109°. The subcooling temperature TC =
109°-93°=16°F
Add charge if the calculated subcooling temperature TC in Step 6 is
lower than the recommended level. Remove and recover the refrigerant
if the subcooling TC is higher than the recommended level. See Table
12 for R-410A saturation temperatures.
See Tables 13 - 16 for unit specific subcooling charts.
See Figure 10 to trace the flow of refrigerant through the system.
FIELD CONNECTED LINE
4-WAY
REVERSING
VALVE
FILTER DRYER
(Solid core)
.
COMPRESSOR
TXV
(Heating)
FIELD CONNECTED LINE
SHOWN IN COOLING POSITION.
035-20401-001 Rev. A (0904)
INDOOR COIL
TXV
(Cooling)
7

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hc5b seriesHl5b series

Table of Contents