Commissioning, inspection, maintenance
Checking the CO
2. Start the boiler and check for leaks.
Danger
Escaping gas leads to a risk of explosion.
Check all gas equipment for tightness.
3. To check the CO
content the burner output can be
2
adjusted manually.
1. Tap MODE.
2. / repeatedly until "SERV" appears.
3. OK to confirm.
OFF appears on the display. Test mode is not
active.
4. Use / to adjust the burner output:
Shown on
display
OFF
_
20
_ _
40
_ _ _
60
_ _ _ _
80
_ _ _ _ _
100
5. Confirm your setting with OK.
The bars stop flashing.
4. Check the CO
content for the upper heating out-
2
put (100 %).
For CO
content limits, see page 24.
2
38
content
(cont.)
2
5. Check the CO
6.
7. Re-check the CO
Burner output
8. Terminate test mode:
0 %
20 %
40 %
60 %
80 %
100 %
9. Shut down the boiler, remove the flue gas analyser
content for the lower heating output
2
(20 %).
The CO
content must be between 0.5 and 0.9 %
2
below the value of the upper heating output.
If the CO
content is within the indicated range,
2
continue with point 8.
If the CO
content lies outside the indicated
2
range, check the balanced flue system for tight-
ness; remedy any leaks.
Replace gas train if required.
content for the upper and lower
2
heating output.
1. / repeatedly until "SERV" flashes.
2. OK to confirm.
The selected value flashes.
3.
repeatedly until OFF flashes.
4. OK to confirm.
When "SERV" disappears, test mode is termi-
nated.
and close flue gas test port