Online/Device
Setup/Detailed Setup
(Continued ...)
Online/Device
Setup/Meterbody
Selections
*This parameter can be changed when PILD is disabled. When PILD is enabled user can still change the
parameter if PILD is in Monitoring mode and not in Training mode
Revision 5.0
PILD/PILD
Select the PILD configuration:
PILD/Application
Provides option for user to select application type so
(App)
that default PILD Configuration parameters for selected
Application Type(SWIN....) are auto selected by
Transmitter.
Possible Application Types are:
PILD/Sampling
The sampling window of PILD in minutes, which
Window (SWIN)
determines a cycle of PILD runs for both training and
monitoring mode.
Enumeration: 3, 6, 9, 12, 15 minutes
PILD/Up Limit
The up limit of PILD factor for normal status.
(UL)*
Valid range is from 0.50 to 1.00.
PILD/Down Limit
The down limit of PILD factor for normal status.
(DL)*
Valid range is from BL to 0.50.
PILD/Blockage
The both sides blockage Limit of PILD factor.
Limit (BL)*
For AP/GP transmitter, BL is not available/applicable,
because there is only one side.
Valid range is from 0.00 to DL.
PILD/Cut Off
Cut Off Frequency (HPF f0) configures the cut off
Frequency
frequency of a high pass filter for dynamic process.
This is used to take noise fluctuation of PV is kept after
filtering.
Valid range is from 0.0 to 5.0..
Displays detailed information pertaining to the
Meterbody, including construction configuration,
materials of construction, fill fluids, and process
connection details.
ST 800 Series HART/DE Option User's Manual
"Enable": enables PILD feature/functionality
"Disable": disables PILD feature/functionality
DP flow application (Not applicable for
Absolute and Gauge Transmitter.
Marine Level
Bubbler Level
Other (Default Factory Configuration)