Concrete curing function

When pipes of floor heating are installed, operation for reinforcing concrete curing is applied.
(Period of operation: 23 days)

Entering procedure

1 After turning off the DIP switch K3 of indoor unit (Default ON), turn off and turn on the indoor unit. The operation for concrete
curing starts automatically. (If blackout occurs and communication restarts later, operation will continue.)
2 Temperature of discharge water is controlled as time goes on like below.
Temp.
60
55
50
45
40
35
30
25
20
1
2
Initial
Classification
Heating
Time
96
72
Temperature
30
55
3 Remaining days are displayed on the wired remote controller during operation but key operation is unavailable.
Remaining
days are
displayed.
∗ If an error is displayed, concrete curing function does not work.
3
4
5
6
7
8
9
10
11
Step raise
24
24
24
24
30
35
40
45
12
13
14
15
16
17
18
19
20
Heating
24
144
24
50
55
50
Day
21
22
23
Step down
24
24
24
24
45
40
35
30
Total
(Hour)
552
-