Standard for pulse emitter
Signal characteristics in accordance with
IEC 62053-31
Adjustable pulse duration
30 - 500 ms
Min. settable time frame
10 ms
Max. switching frequency
17 Hz
Communication
Ethernet port
Design
RJ45 (8P8C)
Suitable cable types
100Base-TX (CAT5)
Grounding of cable required
Protocols supported
Modbus TCP
Transmission rates
10 / 100 Mbit/s, Autonegotiation and Auto-
MDX (Medium Dependent Interface)
Serial gateway
Function
Serial gateway for converting Modbus TCP to
Modbus RTU or SEAbus
Requirements for use
SENTRON PAC RS485 expansion module
Number of devices that can be
max. 31/247 without/with repeaters
operated
Port number
17002 for operation at slot "MOD1"
17003 for operation at slot "MOD2"
Display
Display
Size W x H
72 mm x 54 mm
Update time
0,33 ... 3 sec, adjustable
Connection elements
Measuring inputs and supply voltage inputs
Screw terminals
Tools
PZ2 cal. screwdriver ISO 6789
Crimping tool in accordance with 60947-1
For further data see Fig. 20.
Ring lug terminals
Connection bolt
M3 ... M4, #5 ...#8
The country-specific standards for ring cable lugs must be complied with, e.g.
UL-listed under ZMVV /7, CSA, DIN 46237, IEC 60352-2.
Please observe the instructions of the cable lug manufacturer and
IEC 60352-2 regarding suitable crimp connections. The ring lugs must
be mounted parallel to each other.
Terminal screws
max. vertical screwing force 30 N, 6.75 lbf
Tools
PZ2 cal. screwdriver ISO 6789
Crimping or pressing tool according to manu-
facturer's information for ring lugs
For further data see Fig. 21.
Digital outputs, digital inputs
Screw terminal
Tools
PZ1 cal. screwdriver ISO 6789
Crimping tool in accordance with EN 60947-1
For further data see Fig. 22.
Dimensions and weights
Type of fixing
Panel mounting to IEC 61554
Size W x H x D
96 mm x 96 mm x 82 mm
Cutout (W x H)
92
Overall depth
Without expansion module
77 mm
With expansion module
99 mm
Permissible switching panel thick-
max. 4 mm
ness
Installation location
Vertical
Weight
Device without packaging
approx. 450 g
Device including packaging
approx. 550 g
Degree of protection and safety class
Safety class
II
Degree of protection according to
IEC 60529
Device front
IP65, type 5 enclosure acc. to UL 50
Device rear
Device with screw terminals
IP20
Device with ring lug terminals
IP10
If higher degree of protection requirements are placed on the application engi-
neering, the customer must take suitable measures.
Ambient conditions
Temperature range
Ambient temperature during oper-
– 10 °C ... + 55 °C
ating phase
Ambient temperature during
– 25 °C ... + 70 °C
Transport and storage
Relative humidity
95 % at 25 °C without condensation
(normal conditions)
Installation altitude above sea level
max. 2000 m
6
+0.8
+0.8
mm x 92
mm
Degree of pollution
2
Environmental tests
In accordance with IEC 60068
Further technical data, e.g. measuring accuracy, can be found in the
SENTRON PAC4200 Manual.