Heater Pressure Switch - Roberts Gorden DualAir DAT100 Operation And Service Manual

Heating and cooling units
Table of Contents

Advertisement

SECTION 16: R
R
P
EMOVAL AND
EPLACEMENT
ARTS

16.5 Heater Pressure Switch

Pull off 3 way connector. Spring open plastic clips of
mounting cradle. Replace with correct type of
pressure switch for model. The pressure switches
are colour coded for each pressure setting.
Carry out a commission after working on or
changing a pressure switch.
See Page 21, Section 11.
Pressure Switch
75
90
100
115
RG P/N
90439811
90439807
90439811
90439807
Colour Code
grey
brown
grey
brown
39