SECTION 1: INTRODUCTION 1.1 What is ROBERTS GORDON The ROBERTS GORDON ® ULTRAVAC™ is a micro- processor based control package designed for modulating control of CORAYVAC outdoor temperatures. This controller is capable of giving control outputs to one vacuum pump and three heating zones. The controller also features inputs which are used for indoor and outdoor signal condition monitoring.
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER 1.5 Carton Contents URVSC: ULTRAVAC™ Satellite Controller ULTRAVAC™ Controller Low Voltage 24 V Wiring ULTRAVAC™ Installation Manual (P/N 10081601NA) URVCCL: ULTRAVAC™ Central Controller with TCP/IP Communication Module Low Voltage 24 V Wiring NC C NC C ULTRAVAC™...
Page 9
URVCCM: ULTRAVAC™ Central Controller with Modem Low Voltage 24 V Wiring NC C NC C NC C NC C NC C NC C ULTRAVAC™ Controller with Modem Installed ULTRAVAC™ Software (P/N 10080421) ULTRAVAC™ Software Manual (P/N 10081600NA) ULTRAVAC™ Installation Manual (P/N 10081601NA) Comms Equalization Cable (P/N 10080450) Line Voltage 120 V Wiring...
Page 10
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER URVCCR: ULTRAVAC™ Central Controller with RS-485 Converter Low Voltage 24 V Wiring NC C NC C ULTRAVAC™ Controller with Modem Installed ULTRAVAC™ Software (P/N 10080421) ULTRAVAC™ Software Manual (P/N 10081600NA) ULTRAVAC™ Installation Manual (P/N 10081601NA) Comms Equalization Cable (P/N 10080450) RS-485 Converter Package (P/N 10080430)
1.6 Safety Your Safety is Important to Us! This symbol is used throughout the manual to notify you of possible fire, electrical or burn hazards. Please pay special atten- tion when reading and following the warnings in these sections. Installation, service and annual inspection of controller must be done by an electrician qualified in the installation and service of control systems for heating equipment.
SECTION 2: SPECIFICATIONS 2.1 ROBERTS GORDON ® ULTRAVAC™ Controller 2.1.1 Enclosure Standard Enclosure Construction: 16 gauge painted steel, hinged door, removable knockouts provided. Dimensions: 14.7" w x 17.7" h x 3.5" d NEMA 4 Enclosure (P/N 10080302) Description: NEMA 4 enclosure is sold separately as an option.
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER FIGURE 2: ROBERTS GORDON 120 Vac Outputs Relay Board OUTPUT OUTPUT OUTPUT Plug-In Relays 24 V Input Connections 24 V Board 24 V Power Input Outputs RS 232 Control Direct Connect Board NC C NC C NC C NC C...
2.3 Variable Frequency Drive (VFD) 2.3.1 Enclosure Standard Models Construction: 14 gauge painted steel, mounting panel included, left-hinged door, vented. Dimensions: 12" w x 14 3/8" h x 8" d Protection: UL 50 Type 1, NEMA Type 1 NEMA 4 Models Description: Drive assembly and components fully factory assembled inside NEMA 4...
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER FIGURE 3: Variable Frequency Drive Components (Factory pre-wiring shown) Variable Frequency Drive (1 Ø input model shown) L2/N Terminal Inputs 460 V 3 Ø outputs 120 V signal from relay board NSTALLATION ANUAL 230 V 3 Ø or Relay 120 V output #8...
SECTION 3: INSTALLATION WARNING Severe Injury Hazard Mount controls with materials with a minimum working load of 75 lbs (33 kg). Failure to follow these instructions can result in death, injury or property damage. Installation of the ROBERTS GORDON ULTRAVAC™ Controller and the associated external electrical wiring must be done by an electrician qualified in the installation of control systems for heating equipment.
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER 3.3 Cable Requirements: 3.3.1 Line Power Supply: As per individual building specification for class of cable to be used. Use copper conductors only. To size the cable, use the amperages of the burners given on Page 13, Section 3.4.1, for each individual zone.
3.4 Electrical Installation Requirements DANGER Electrical Shock Hazard Disconnect electrical before servicing. This appliance must be connected to a properly grounded electrical source. Replace cover before operating. Failure to follow these instructions can result in death or electrical shock. 3.4.1 The enclosure must be supplied from a local fused isolator rated for a total amperage not exceeding 25 A.
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER 3.7 Indoor Sensor Placement The sensor measures the air temperature in the building. It is important that the sensor is located in an area within the heated zone at occupant level. For the most accurate results, sensors should be mounted on an inside wall, away from any air vents or other sources of heat and cold.
SECTION 4: TYPICAL EXTERNAL DIAGRAMS FIGURE 10: Central Controller Communication Equalization Wiring All ULTRAVAC™ Central Controllers are shipped with a communication equalization cable (P/N 10080450). The cable is supplied to equalize and balance the circuitry of the communications on the controller network that may be experiencing noise or transient voltage levels. Connect the communi- cation equalization cable as shown below to the first or the last controller on the data bus.
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER FIGURE 11: ROBERTS GORDON Zone 1 Zone 2 Sensor Sensor (see NOTE 6) (see NOTE 6) Electrical wiring connections indicated by a dot; Ground Shield (one end only) indicated by; Separate line and low voltage circuits. Do not run line voltage wiring through bottom section of enclosure that houses the control board.
Page 23
ROBERTS GORDON ® ULTRAVAC™ Central Controller External Wiring (continued) Continued From Previous Page VFD Assembly ( 1 Ø input VFD model shown) L2/N Terminal 5 Terminal 2 Zone 3 Burners VFD Power Supply (1 Ø input VFD model shown, see NOTE 3) To Terminals M16/12.P M16/12.P...
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER FIGURE 12: ROBERTS GORDON Zone 1 Zone 2 Sensor Sensor (see NOTE 6) (see NOTE 6) Electrical wiring connections indicated by a dot; Ground Shield (one end only) indicated by; Separate line and low voltage circuits. Do not run line voltage wiring through bottom section of enclosure that houses the control board.
Page 25
® ROBERTS GORDON ULTRAVAC™ Satellite Controller External Wiring (continued) Continued From Previous Page VFD Assembly ( 1 Ø input VFD model shown) L2/N Terminal 5 Terminal 2 Zone 3 Burners VFD Power Supply (1 Ø input VFD model shown, see NOTE 3) To Terminals M16/12.P M16/12.P...
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER SECTION 5: COMMUNICATIONS One ROBERTS GORDON ® ULTRAVAC™ Controller per building (called the "central controller) must have equipment for remote communications to a PC. This equipment consists of either a modem chip, an RS- 485 converter, or a TCP/IP communications module.
5.2 RS-485 Converter for Central Controller For remote on-site viewing of system status and settings of any controller, use the RS-485 converter to connect a single PC (9 pin serial port) to the RS- 485 terminals on the Central Controller. This will allow communication between one PC and any of the ULTRAVAC™...
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER 5.3 TCP/IP Communication Module For remote on-site viewing of system status and settings of any controller, use the TCP/IP communi- cation module to connect the controllers to a Local Area Network (LAN) via Ethernet cable. Any computer on the LAN that has ULTRAVAC™...
FIGURE 16: TCP/IP Communication Module Wiring Shrinkwrap RS-232 RS232 DIRECT AUX POWER Direct Port Dip Switch #1 set to ON UNIVERSAL INPUTS It is important that the module power wire is connected as shown (black=5 V- / red= 5 V+) wire orientation. Make sure to verify connection before connecting to the control board.
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER 5.4 Direct Connect For local viewing of system status and settings of any controller, a portable PC can be connected. Using the 9 pin adapter provided, (See Page 24, Figure 17), you may wire from your computer serial port to the RS-232 direct connect port on the control board via standard 4-wire phone cable.
5.5 Communications Between Multiple ROBERTS GORDON If more than one ROBERTS GORDON VAC™ Controller is installed in a building, the controllers’ RS-485 communications must be wired in series. See Page 25, Figure 18. Connect the RS-485 terminal on controller 1 to the RS-485 terminal on controller 2 and so on in a daisy chain fashion.
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER 5.5.1 Repeater If the RS-485 communications wire length is above 4000', a repeater must be used to extend the signal. The repeater can also be used to create parallel branches of ROBERTS GORDON communications bus wiring. Each repeater is sold in a 12" x 12" NEMA 1 enclosure with a 120/24 Vac transformer.
SECTION 6: VARIABLE FREQUENCY DRIVE PROGRAMMING 6.1 VFD Parameter Settings For Use With ® ROBERTS GORDON ULTRAVAC™ The VFD parameters come with factory default set- tings. The following parameter settings must be changed for ROBERTS GORDON Settings can only be altered when the pump motor is stopped.
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER the password must be entered in order to access the parameters again. 6.2 Altering VFD Parameters Using the procedure described in Section 6.1.1 through Section 6.1.5, alter the following parameters: Parameter Parameter Factory Number Name Units Ending Password...
SECTION 7: COMMISSIONING THE CORAYVAC NOTE: The ROBERTS GORDON software must be installed on the PC, the communi- cation connection must be made to the controller and all wiring of the ROBERTS GORDON control boards, relay boards, burners, pumps and VFD must be completed before starting the commis- sioning procedure.
SECTION 7: C CORAYVAC ® OMMISSIONING YSTEM FIGURE 21: Possible Damper Couplings’ Locations...
Page 38
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER Step 7.1.3 After setting end vent vacuums between 2.5" wc and 3.0" wc, while all the burners are still operating, use the down arrow button on the VFD to reduce the frequency of the output signal to the pump.
SECTION 8: REPLACEMENT PARTS 8.1 ROBERTS GORDON ® ULTRAVAC™ Controller Replacement Parts Caution: Use only genuine ROBERTS GORDON Roberts-Gordon voids warranty. FIGURE 22: ROBERTS GORDON OUTPUT OUTPUT Plug-In NC C NC C NC C NC C NC C NC C NC C NC C Description...
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER Description Comms Equalization Cable (not shown, located only on Central Controller) Telephone Sharing Device, 4 port Relay 120 V Unitary Lights for 150 Style Control Board Lamp Green Enclosure Mount w/o Light Lamp Red Enclosure Mount w/o Light Light Diode 24 Vac 8.2 Variable Frequency Drive Replacement Parts Caution: Use only genuine ROBERTS GORDON...
Description Rotary Disconnect Handle (not shown) Rotary Disconnect Rod (not shown) 8.3 Replacement Parts Instructions DANGER Electrical Shock Hazard Disconnect electrical before servicing. This appliance must be connected to a properly grounded electrical source. Replace cover before operating. Failure to follow these instructions can result in death or electrical shock.
ROBERTS GORDON ® ULTRAVAC™ C ONTROLLER NSTALLATION ANUAL 8.3.6 Variable Frequency Drive 25 A or 10 A Fuse To replace a fuse, turn off input power to the variable frequency drive assembly at the breaker or disconnect switch. Turn off 120 V power to the relay board inside the ROBERTS GORDON ®...
SECTION 10: THE ROBERTS GORDON ROBERTS-GORDON WILL PAY FOR: Within 42 months from date of shipment from Roberts- Gordon, replacement parts will be provided free of charge for any part of the controller which fails due to a manufacturing or material defect. Roberts-Gordon will require the part in question to be returned to the factory.