Download Print this page

Bosch D8132 Installation Manual page 6

Battery charger modules

Advertisement

6
en | Wiring
4
Wiring
4.1
Wiring for extending battery standby time and providing
additional auxiliary current output
If the module is to be connected to a control panel to increase stand by time, refer to the
appropriate control panel's Installation and Operation Guide to calculate the total battery
Ampere-hours (Ah) required for your system. The recharge time cannot exceed 48 hours for UL
listed applications. Once satisfactory recharge time, standby time, Ampere-hour, and auxiliary
current values are identified, determine the combination of batteries required for your
application using the following table.
1050 mA
Tab. 4.1: Battery requirement
Figure 4.1: Wiring for extended battery standby time and providing additional auxiliary current output
2018.05 | 4.0 | F.01U.036.305
24 standby hours
Aux
Recharge
current
time (hrs)
load
430 mA
9
550 mA
10
680 mA
11
800 mA
14
930 mA
17
21
1 AC circuit common to both
transformers
3 Control panel
60 standby hours
Aux
Recharge
current
time (hrs)
load
N/A
N/A
50 mA
7
100 mA
9
150 mA
10
200 mA
12
250 mA
14
2 Transformers*
4 D122 Dual battery harness
Installation manual
Battery charger modules
72 standby hours
Aux
Recharge
current
time (hrs)
load
N/A
N/A
10 mA
7
50 mA
9
90 mA
10
130 mA
12
180 mA
13
Bosch Security Systems, Inc.
Total
battery
Amp-hrs
(Ah)
12
15
18
21
24
27

Advertisement

loading

This manual is also suitable for: