R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L
Table 50. 59PS technical data
Characteristic
Operation accuracy
Pickup time
V
= 1.1 x set Pickup value
1) 2)
Fault
Reset time
Reset ratio
Retardation time
Trip time accuracy in definite time mode
Suppression of harmonics
Positive sequence voltage before fault = 0.0 x Vn, fn = 60 Hz, positive sequence voltage with nominal frequency in-
1)
jected from random phase angle, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
2)
Table 51. 32P technical data
Characteristic
Operation accuracy
Table 52. 32N technical data
Characteristic
Operation accuracy
Value
Depending on the frequency of the current measured: f
±1.5% of the set value or ±0.002 x V
Minimum
29 ms
< 40 ms
Typical 0.96
< 35 ms
±1.0% of the set value or ±20 ms
DFT: -50dB at f = n x f
, where n = 2, 3, 4, 5,...-
n
Value
Depending on the frequency of the current measured: f
±1.5% of the current or ±0.01A
±1.5% of the voltage or ±1V
±3.0% of the characteristic angle or ±4 Deg
Value
Depending on the frequency of the current measured: f
±1.5% of the current or ±0.01A
±1.5% of the voltage or ±1V
±3.0% of the characteristic angle or ±4 Deg
±2Hz
n
n
Typical
31 ms
±2Hz
n
±2Hz
n
Maximum
32 ms