28
R E R 6 2 0 A D VA N C E D R E C LO S E R P R OT E C T I O N & C O N T R O L
Protection functions
—
Table 37. IA, IB, IC technical data
Characteristic
Operation accuracy
Suppression of harmonics
—
Table 38. VA, VB, VC
Characteristic
Operation accuracy
Suppression of harmonics
—
Table 39. IG technical data
Characteristic
Operation accuracy
Suppression of harmonics
—
Table 40. VN technical data
Characteristic
Operation accuracy
Suppression of harmonics
—
Table 41. I1, I2, I0 technical data
Characteristic
Operation accuracy
Suppression of harmonics
Value
Depending on the frequency of the voltage measured: f
±0.5% or ±0.002 x I
n
(at currents in the range of 0.01 to 4.00 x I
Note: The protection and control relay may indicate non-zero phase current measurements in the
range of 0.003...0.01 x In when the recloser is in the open state.
DFT: -50dB at f = n x f
, where n = 2, 3, 4, 5,...
n
RMS: No suppression
Value
Depending on the frequency of the current measured: f
At voltages in range 0.01 to 4.00 x I
±0.5% or ±0.002 x V
n
DFT: -50dB at f = n x f
, where n = 2, 3, 4, 5,...
n
RMS: No suppression
Value
Depending on the frequency of the current measured: f/f
±0.5% or ±0.002 x I
n
at currents in the range of 0.01 to 4.00 x I
DFT: -50dB at f = n x f
, where n = 2, 3, 4, 5,...
n
RMS: No suppression
Value
Depending on the frequency of the current measured: f/f
±0.5% or ±0.002 x V
n
DFT: -50dB at f = n x f
, where n = 2, 3, 4, 5,...
n
RMS: No suppression
Value
Depending on the frequency of the current measured: f/f
±1.0% or ±0.002 x I
n
at currents in the range of 0.01 to 4.00 x I
DFT: -50dB at f = n x f
, where n = 2, 3, 4, 5,...
n
±2Hz
n
)
n
±2Hz
n
n
= ±2Hz
n
n
= ±2Hz
n
= ±2Hz
n
n