ABB RER620 Product Manual page 19

Advanced recloser protection & control
Hide thumbs Also See for RER620:
Table of Contents

Advertisement

Table 8. Energizing inputs
Description
Rated frequency
Current inputs
Rated current, I
Thermal withstand capability:
- Continuously
- For 1 s
Dynamic current withstand:
- Half-wave value
Input impedance
Voltage input
Rated voltage
Voltage withstand:
- Continuous
- For 10 s
Burden at rated voltage
1) Ordering option for ground current input
2) Ground current and/or phase current
Table 9. Binary inputs
Description
Rated voltage
Operating range
Current drain
Power consumption
Threshold voltage
Reaction time
Table 10. Signal outputs and IRF output
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry 0.5 s
Breaking capacity when the control-circuit time constant L/R<40 ms, at
48/110/220 V DC
Minimum contact load
Table 11. Double-pole power output relays with TCM function
Description
Rated voltage
Continuous contact carry
Make and carry for 3.0 s
Make and carry 0.5 s
Breaking capacity when the control-circuit time
constant L/R<40 ms, at 48/110/220 V DC (two
contacts connected in series)
Minimum contact load
Trip-circuit monitoring (TCM):
- Control voltage range
- Current drain through the monitoring circuit
- Minimum voltage over the TCM contact
Value
50/60 Hz ± 5 Hz
0.2/1 A
n
4 A
100 A
250 A
<100 mΩ
100 V AC/ 110 V AC/ 115 V AC/120 V AC (Parametrization)
2 x Vn (240 V)
3 x Vn (360 V)
<0.05 VA
Value
250 V AC/DC
8 A
15 A
30 A
5 A/3 A/1 A
100 mA at 24 V AC/DC
20...250 V AC/DC
~1.5 mA
20 V AC/DC (15 to 20 V)
1)
Value
24 to 250 V DC
±20 % of the rated voltage
1.6 to 1.9 mA
31.0 to 570 mW
18 to 176 V DC
3 ms
Value
250 V AC/DC
5 A
10 A
15 A
1 A/0.25 A/0.15 A
100 mA at 24 V AC/DC
1/5 A
2)
20 A
500 A
1250 A
<20 mΩ
19