Glassbreak detector
Hide thumbs Also See for FlexGuard FG-1625F:

Advertisement

FlexGuard
Refer to Installation Instructions and diagrams (next page) when installing this product
1. General Information
The FG-1625F flush mount glassbreak detector senses
the sound of breaking plate, tempered, laminated, wired,
coated and sealed insulating glass.
This product is UL and ULC listed.
2. Choosing Mounting Location
The preferred mounting location for the device is on a
wall or ceiling, opposite the protected glass.
For the best detector performance, select a mounting
location that is:
• within 7.6 m (25 feet) of the protected glass;
• within clear view of the protected glass;
• at least 2 m (6.5 feet) from the floor;
• at least 1 m (3.3 feet) from forced air ducts;
• at least 1 m (3.3 feet) from sirens or bells greater
than 5 cm (2 inches) in diameter.
• between the protected glass and any heavy
window coverings that may be present.
Alternatively, when heavy window coverings are
present, the detector can be mounted on the frame
of the window.
Avoid mounting the detector on the same wall as the
protected glass, on free-standing posts or pillars, or in
rooms with noisy equipment (air compressors, bells,
power tools, etc.), if this equipment is operated when
the detector is armed.
3. Testing Mounting Location With 9V Battery
You may test the detector in the desired mounting
location before drilling/wiring. If the 9V battery cannot
supply sufficient power, the detector will not operate
and the red and green LEDs will flash on/off.
Follow the procedure described in "Testing the
Detector" (below) to confirm proper operation.
4. Configuring Sensitivity (Range)
DIP switches SENS1 and SENS2 set detector
sensitivity (range), as shown:
SENSITIVITY
RANGE *
MAX
7.6m (25 ft)
MEDIUM
4.6m (15 ft)
LOW
3m (10 ft)
LOWEST
1.5M (5 ft)
*
Sensitivity must be set to match the distance between
the detector and the protected glass, as verified using
the FG-701 Glassbreak Simulator.
5. Configuring LED Switch
The LATCH and LED DIP switches determine LED
indicator operation.
SWITCH
OFF
LATCH
Red LED lights for 5
seconds during alarm
LED
LEDs disabled (except for
3
power up and test mode
)
1
Alarm relay timing is not affected by the latched Alarm LED.
2
Reset the Alarm LED by removing/restoring power, or by toggling the
detector in and out of Test Mode.
3
LEDs can be enabled/disabled using FG-701.
6. Preparing Mounting Location
The FG-1625F is designed for flush mounting using a
standard US or Canadian electrical junction box. Once
you have selected the appropriate mounting location,
install a junction box.
7. Wiring the Detector
Refer to the wiring diagrams (page 1) to select the
appropriate wiring configuration.
NOTE: This sensor must be connected to a UL Listed
power supply or UL Listed control unit capable of
supplying a minimum of four hours of standby power.
8. Mounting the Detector
Using appropriate screws (not supplied), mount the
detector to the junction box. When not using a
junction box, use wall anchors for mounting in sheet
rock.
9. Testing the Detector
The detector should be tested at least once each year.
Test the detector with the FG-701 Glassbreak Simulator.
The model FG-700 Glassbreak Simulator can also be
used if it is set for the TEMPered glass sound. Other
simulators will not give accurate indication of range.
Always test detector with cover in place.
®
FG-1625F Glassbreak Detector Supplemental Information
To enter Test Mode manually:
1.
Remove the front cover.
2.
Use a screwdriver to short the Test Mode
pads on the PC board (see diagram on next
page).
3.
Close the front cover.
The detector's green LED blinks approximately once per
second to indicate that it has entered Test Mode.
To enter the Test Mode with the FG-701:
1.
Stand within 4.6 m (15 feet) of the detector.
2.
Switch the FG-701 to ACTIVATE and MANual
modes.
3.
Point the front [speaker] of the glassbreak
simulator towards the detector. Press the red
START button to send a short activation code.
When the detector enters Test Mode, the green LED
on the detector flashes about once per second. If the
green LED does not flash, move closer to the detector
and repeat the procedure.
Testing the Detector (flex and audio signals):
To test the detector using the FG-701:
1.
Place the detector in Test Mode.
2.
Set the FG-701 switches to the TEST and
FLEX positions.
3.
Position the FG-701 near the farthest point of
the protected glass, and point the speaker
directly at the detector. If window coverings
are present, close them fully and hold the FG-
701 between the coverings and the protected
glass.
4.
Press the red START button. The simulator
clicks on and starts an 8-second armed
period.
5.
Generate a flex signal by carefully striking the
glass with a cushioned tool. The FG-701
responds with a burst of glassbreak audio.
If the detector receives both the flex and audio signals
properly, its red Alarm LED lights for five (5) seconds.
SENS1
SENS2
(Red Alarm LED does not latch in Test Mode).
OFF
OFF
ON
OFF
Testing the Detector (audio signals only):
OFF
ON
The FG-701 can also be used to test the detector's
ability to receive audio signals only. See the FG-701
ON
ON
Operating Instructions for additional information. When
it receives the audio signal, the detector flickers its
green Event LED.
Exiting Test Mode:
When you have finished testing, exit Test Mode by
following the same procedure used to enter Test Mode.
The FG-1625F automatically exits Test Mode five
ON
minutes after the last event is detected.
Red LED latches ON when
1, 2
detector goes into alarm
LEDs always enabled
10. LED Indicators
The detector is equipped with two LEDs: a green Event
LED and a red Alarm LED. When the LEDs are
enabled, they light in a variety of patterns to indicate
the detector's status. The following table summarizes
the LED messages.
CONDITION
Normal
Normal, event detected
Normal, break detected
Normal, alarm latched
Power up
Low Voltage
Test Mode
Test Mode, event detected
Test Mode, alarm
11. Remote LED Enable/Disable Mode
The detector's Remote LED Enable/Disable Mode allows
you to enable or disable the detector's LEDs with the
FG-701 Glassbreak Simulator.
To enable or disable the LEDs with the FG-701:
1.
Set LED switch, S4 position 4, to off.
2.
Enter Test Mode, and then exit Test Mode.
3.
Within two (2) seconds, enter Test Mode
again; this changes LED enable/disable status.
4.
Exit Test Mode again.
5.
Clap your hands to test the LEDs. If enabled,
the green LED will flicker. If disabled, the
green LED will remain off.
©2002 Honeywell International Inc. All rights reserved.
Honeywell, FlexGuard and IntelliSense are registered trademarks of
Honeywell International Inc. - All other brands mentioned are the
trademarks or registered trademarks of their respective owners.
Specifications subject to change without prior notice.
12. Specifications
13. Nominal Glass Thickness Chart
*
framed in the wall or mounted in a barrier at least 0.9m (36 in.) wide.
1
Protected only if both plates in the unit are broken
2
Coated glass with security films up to 0.35mm (14 mils) thick (including
films for solar protection) may be used. Evaluated with the these
products: 3M
ply film; Film Technologies International, Inc.'s GLASS-GARD GGLL
1200 has been evaluated with this product by Underwriters
Laboratories, Inc.
3
In compliance with Underwriters Laboratories of Canada's Standard
for Intrusion Detection Units (CAN/ULC-S306-M89):
4
5
FCC NOTICE: This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This deice may
not cause harmful interference, and (2) this device must accept any
interference received, including interference that may cause undesired
operation.
The user is cautioned that changes or modifications not expressly
approved by Honeywell could void the user's authority to operate this
equipment.
NOTE: This equipment as been tested and found to comply with the
GREEN LED
RED LED
limits for a Class B digital device, pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protection
OFF
OFF
against harmful interference in a residential installation.
Flicker
OFF
equipment generates, uses and can radiate radio frequency energy
and, if not installed and used in accordance with the instructions, may
OFF
ON 5 seconds
cause harmful interference to radio communications. However, there
OFF
ON
is no guarantee that interference will not occur in a particular
installation. If this equipment does cause harmful interference to radio
ON 1 second
ON 1 second
or television reception, which can be determined by turning the
Flash ON/OFF
Flash ON/OFF
equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures: 1) Reorient or
Flash once per sec
OFF
relocate the receiving antenna; 2) increase the separation between the
equipment and receiver; 3) connect the equipment into an outlet on a
Flicker
OFF
circuit different from that to which the receiver is connected; 4) consult
Flash once per sec
ON 5 seconds
the dealer or an experienced radio/television technician for help.
IC Notice: This Class B digital apparatus complies with the Canadian
ICES-003.
Cet appareil numérique de la Classe B est conforme à la norme NMB-
003 du Canada
Range:
ESD Immunity:
7.6 m (25 ft.) maximum, omni-
10 kV discharges of either
directional
polarity to exposed surfaces
No minimum range
Power Requirements:
Operating Temperature:
6 - 18 VDC; 12 mA typical at
-10° to 50° C (14° to 122° F)
12 VDC, 22 mA max, (Latched
Storage: -20° to 50° C
LED) AC Ripple: 4 Volts
(-4° to 122° F)
peak-to-peak at Nominal 12
VDC
Alarm Duration:
5 seconds (unaffected by
Dimensions:
alarm LED latching)
Face Plate
(4.9 in. H x 3.3 in. W x 0.53 in. D)
Alarm Relay:
FG-1625F Form A
Rear Housing
(2.8 in. H x 1.6 in. W)
125 mA maximum
25 VDC maximum
Weight:
98 g (3.5 oz.)
ON/closed 22Ω ±1Ω
Packaged Product: 126 g (4.5 oz.)
OFF/open >1MΩ
Approvals / Listings:
Tamper Switch:
FCC and IC verified
Cover tamper
UL Listed, ULC Listed
25 mA maximum
CE, C-Tick
24 VDC maximum
EN 50131-1; Security Grade
RFI Immunity:
2, Environmental Class II
30 V/m,
Suitable for connection to an
10 MHz - 1000 MHz
EN60950 Class II Limited
Power Source
Nominal Thickness
Glass Type*
Minimum
3a, 3b, 4
Plate
2mm (3/32 in.)
Tempered
3mm (1/8 in.)
3b
Laminated
3mm (1/8 in.)
Wired
6mm (1/4 in.)
2,3b
3mm (1/8 in.)
Coated
1,5
Sealed Insulating
3mm (1/8 in.)
[13mm (1/2 in.)
overall]
Minimum size for all types is 28cm (11 in.) square; glass must be
®
®
SCOTCHSHIELD
SH14CLARL – 0.35mm (14 mils), 4
Plate glass 3mm (1/8 in.) to 10mm (3/8 in.) can be used.
a.
ULC recognizes a maximum range for protecting coated, 3mm
b.
(1/8 in.) laminated, and 2mm (3/32 in.) plate glass of 3.8m
(12.5 ft.); sensitivity should be set at maximum.
Minimum of 3mm (1/8 in.) plate glass is to be used in UL installations.
UL recognizes a maximum range for protecting sealed insulating
glass of 6.1m (20 ft.) with sensitivity set at maximum.
NOTICES
Ê5-051-737-00CaŠ
:
125 x 84 x 70mm
:
70 x 42mm
Maximum
10mm (3/8 in.)
10mm (3/8 in.)
14mm (9/16 in.)
6mm (1/4 in.)
6mm (1/4 in.)
6mm (1/4 in.)
[19mm (3/4 in.)
overall]
This
5-051-737-00 Rev C