8
Installation Instructions

Power Supply Wiring

TIP
1. Place the input voltage jumper to match the input voltage. (This does not
apply to the 1746-P3, 1746-P5, 1746-P6, and 1746-P7 power supplies, which
do not have a jumper.)
ATTENTION
!
WARNING
!
Fuse
Jumper Selection
100/120 Volts
200/240 Volts
Publication 1746-IN004B-EN-P - March 2008
For more information on wiring, see Allen-Bradley
Programmable Controller Grounding and Wiring Guidelines,
publication 1770-4.1.
Refer to publication 1746-IN016, for chassis installation and
grounding requirements.
Set the input jumper before applying power. Hazardous
voltage is present on exposed pins when power is
applied; contact with the pin may cause injury to
personnel.
If you connect or disconnect the wiring to the terminal
blocks or if you insert or remove the power supply while
power is on, an electrical arc can occur. This could cause
an explosion in hazardous location installations. Be sure
that power is removed or the area is nonhazardous
before proceeding.
Catalog Numbers
1746-P1 & 1746-P2
Jumper Selection
85-132V ac
170-250V ac
Catalog Number
1746-P4