S9200U1000 UNIVERSAL HOT SURFACE IGNITION INTEGRATED FURNACE CONTROL
a
Flash Code
Amber LED Status Code and Error Description
OFF
Control powered - No flame
Heartbeat
Control powered - Call for heat - Flame present
Call for heat - Low flame current
b
Periodic Blink
Heartbeat
Call for heat - Flame sense out of sequence - Flame still present Check/Repair: Flame at burners, if present replace gas valve.
OFF
All other conditions
a
Flash Code Descriptions:
- Pulse: A 0.25 second flash followed by 3.75 seconds of off time.
- Heartbeat: Constant 0.5 second bright 0.5 second dim cycles.
- Periodic Blink: 0.5 second on, 0.5 second off. During local history recall, this fault is flashed as a 1 + 2 pattern.
b
During local history recall, this fault is flashed as a 1 + 2 pattern.
Flash
Red LED Status Code and Error
a
Code
Description
Pulse
Control powered (Standby; No Call for
Heat)
Heartbeat Call for Heat - Normal operation
Pressure Switch Codes
2
Pressure Switch failed Open
3
Pressure Switch failed Closed
4
Pressure Switch opened during Trial For
Ignition or Run Mode
Limit Code
5
Limit switch open
Flame Code
6
Unexpected flame - Waiting for flame to be
off after the 20 second delay
Soft Lockout Codes
2 + 1
Soft Lockout - Exceed maximum number
of retries
2 + 3
Soft Lockout - Exceeded maximum
number of recycles or retries where the
last recycle/retry was due to the pressure
switch opening
2 + 4
Soft Lockout - Exceeded maximum
number of recycles where the last recycle
was due to a flame failure
2 + 5
Soft Lockout - Exceeded maximum
number of recycles where the last recycle
was due to the limit circuit opening or the
limit remained open longer than three
minutes
2 + 6
Soft Lockout - Gas Valve Failed to Make
69-2075EF—01
Table 11. Flame Status Codes (Amber LED).
Table 12. Control Status Codes (Red LED).
Not Applicable
Not Applicable (normal operation)
Check: If inducer is running, inducer could be broken or disconnected, or inducer relay
K4 may have failed.
Check/Repair: Low line voltage; Pressure switch wiring loose; hose disconnected or
leaking; water in hose; venting blocked or obstructed.
Check: If inducer is off; inducer relay (K4) could be welded.
Check/Repair: Terminal wiring (shorted); pressure switch contacts (closed when should
be open); pressure switch hoses have water build-up or obstruction.
Check: See if inducer is running.
Check/Repair: Restricted venting; low input voltage; water in horizontal vent length.
Check: Wiring; restricted airflow through heat exchanger; clogged filters; slow circulator
fan speed.
Repair: Remove restrictions. Increase airflow through furnace (increase motor speed,
open more ducts, add more returns).
Check/Repair: Gas valve leakage.
Check/Repair: Gas supply (pressure, supply, shut-off valves, gas valve); ignition (HSI
element not properly positioned and glowing); flame sensing (lead-wire broken or
grounded, flame rod not properly positioned, or flame rod contamination); low line
voltage.
Check/Repair: Pressure switch wiring; slow inducer; restricted, excessive, or obstructed
venting; unstable line voltage.
Check/Repair: Gas supply; flame sensor wiring.
Check: Wiring; restricted airflow through heat exchanger; clogged filters; slow circulator
fan speed.
Repair: Remove restrictions. Increase airflow through furnace (increase motor speed,
open more ducts, add more returns).
Check/Repair: Gas valve, Gas valve wiring.
Replace S9200U1000 if problem persists.
Not Applicable (normal operation)
Not Applicable (normal operation)
Check: Flame rod for contamination or loose wiring; low gas
pressure.
Not Applicable
Check / Repair
20
Check / Repair