Installation Guide
Test
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-5
EMC Immunity Type Tests per IEEE 1613
NOTE
The RUGGEDCOM RS900 meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports. Class 1 allows for temporary communication loss, while Class 2 requires
error-free and interrupted communications.
EMC and Environmental Type Tests
Description
Induced (Conducted) RFI
Magnetic Field
Voltage Dips and Interrupts
IEC 61000-4-11
Damped Oscillatory
Mains Frequency Voltage
Ripple on DC Power Supply
Dielectric Strength
HV Impulse
AC Power Ports
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
Signal Ports
DC Power Ports
AC Power Ports
Earth
Ground Ports
Enclosure Ports
40 A/m Continuous
DC Power Ports
Voltage Dips
100% for 5 Periods
and Interrupts
100% for 50 Periods
Signal Ports
2.5 kV Common Mode @ 1 MHz
1 kV Differential Mode @ 1 MHz
DC Power Ports
2.5 kV Common Mode @ 1 MHz
1 kV Differential Mode @ 1 MHz
AC Power Ports
2.5 kV Common Mode @ 1 MHz
1 kV Differential Mode @ 1 MHz
Signal Ports
DC Power Ports
DC Power Ports
Signal Ports
2 kV (Failsafe Relay Output)
DC Power Ports
AC Power Ports
Signal Ports
5 kV (Failsafe Relay Output)
DC Power Ports
AC Power Ports
Test Levels
10 V
10 V
10 V
10 V
1000 A/m for 1 s
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
30 V Continuous
300 V for 1 s
30 V Continuous
300 V for 1 s
10%
1.5 kV
2 kV
5 kV
5 kV
Chapter 6
Certification
Severity Levels
4
3
3
3
3
3
3
3
4
4
3
29

Hide quick links: