Control Systems
Individual control systems
I
I
3. Wired remote controller
MWR-WE10N
4) Option function
B
uilt-in temperature sensor of wired remote controller
(1) When communication error occurs over 3 minutes,
Indoor unit ignores the built-in temperature sensor and use indoor unit temperature sensor.
Ignores the temperature compensation setting on the wired remote controller and use the compensation value set on indoor
unit instead.
(2) When communication resumes,
Built-in temperature use is recovered.
Setting must be done again to use the temperature compensation.
E
N(ERV) : N(Indoor unit)
By comparing indoor room temperature, setting temperature and outdoor temperature, wired remote controller changes
remote controller option setting.
22