Control Systems
Building management system
VI
VI
1. DMS L-net (Lonworks GW)
MIM-B18N
10) Network parameter chart
(1) Indoor unit/ ERV/ AHU kit object
nviOnOff SNVT_switch
nviApplicMode SNVT_hvac_mode
nviSetPoint SNVT_temp_p
nviFanStatus SNVT_switch
nviERVMode SNVT_count
nviFilterReset SNVT_switch
nviUserLockout SNVT_switch
nviOccOpMode SNVT_switch
nviCoolTempLock SNVT_switch
nviHeatTempLock SNVT_switch
(2) DMS system object
nviDigitalOut[6]_switch
nviAllOff SNVT_hvac_emerg
154
SSACIndoor[nn](objectid=1-128)
nvoSpaceTemp SNVT_temp_p
nvoApplicMode SNVT_hvac_mode
nvoOccOpMode SNVT_switch
nvoCoolTempLock SNVT_switch
nvoHeatTempLock SNVT_switch
nvoUserLockout SNVT_switch
nvoEnergyConp SNVT_elec_kwh_I
nvoEnergyCon SNVT_elec_kwh_I
nvoRuntimep SNVT_time_hour
nvoRuntime SNVT_time_hour
nvoDevListDesc SNVT_str_asc
SSACSystem(objectid=129)
nvoDigitalOut[6] SNVT_switch
nvoSystemLock SNVT_switch
nvoSystemAlarm SNVT_count
Configuration Properties
nciSndHrtBt
nciMinOutTm
nciMinDelta Temp
nciDelayStartup
nvoSetPoint SNVT_temp_p
nvoOnOff SNVT_switch
nvoFanStatus SNVT_switch
nvoERVMode SNVT_count
nvoErrorCode SNVT_count
nvoDeviceAlarm SNVT_state
nvoDigitalIn[8] SNVT_switch
nvoDMS2Alarm SNVT_count