Note 1 :
Symptoms of incorrect connection of BC controller pressure sensor to the board
Cooling-only
Normal
Note 2 :
Check using LED monitor display switch (heat source unit MAIN board SW1)
Note 3 :
Check CNP1 (liquid measurement) and CMP3 (intermediate) connectors on BC controller board for disconnection or
looseness.
Note 4 :
With the sensor of the applicable connector removed from the board, use the LED monitor display switch (Note 1) to
check the pressure value.
Pressure Sensor Replacement Precaution
Cooling-principal
Insufficient
SC11 large
cooling.
SC16 small
PHM < 0
Measured Data
High pressure
Low pressure
BC controller pressure
(liquid measurement)
(intermediate)
(Pressure sensor output voltage)
Symptom
Heating-only
Warm indoor SC
SC11 small
small. Warm in-
SC16 small
door thermo ON
PHM < 0
especially noise.
Signal
SW1 Setting
HPS
1
2 3 4 5 6 7 8 9 10
ON
LPS
1
2 3 4 5 6 7 8 9 10
ON
1
2 3 4 5 6 7 8 9 10
PS1
ON
1
2 3 4 5 6 7 8 9 10
PS3
ON
–89–
Heating-principal
Insufficient heating
SC11 large
Warm indoor SC small
SC16 small
Warm indoor thermo
PHM < 0
ON especially noise