Mitsubishi Electric PQRY-P200YEM-A Service Handbook page 38

City multi
Table of Contents

Advertisement

1
Classification
Portion
Transmission
1
Limitation of transmission line length followed? For
line
example, 200m or less (total length : 500m) at the farthest.
2
1.25mm
(Remote controller 10m or less 0.75mm
3
2-core cable used for transmission line?
4
Transmission line apart from power source line by 5cm or more?
5
One refrigerant system per transmission line?
6
The short circuit connector is changed form CN41 to
CN40 on the MAIN board when the system is centralized
control? (Just one outdoor unit. Not all outdoor units.)
• No connection trouble in transmission line?
7
8
Connection of wrong remote controller line terminals?
• MA Remote controller : TB15
• M-NET Remote controller : TB5
System set
Address setting properly done? (M-NET Remote
1
controller, indoor unit and outdoor unit.)
Setting of address No. done when shutting off power
2
source?
Address numbers not duplicated?
3
Turned on SW3-8 on indoor unit circuit board when
4
mounting room thermistor sensor?
Before starting
Refrigerant piping ball valve (Liquid pressure pipe, gas
1
pressure pipe) opened?
2
Turn on power source 12 hours before starting operations?
1Hr.
CENTRALLY CONTROLLED
˚C
ON OFF
D A I L Y
AUTO OFF
CLOCK
FILTER
CHECK
REMAINDER
CHECK MODE
TEST RUN
STAND BY
˚C
LIMIT TEMP.
DEFROST
ERROR CODE
NOT AVAILABLE
TEMP
ON/OFF
ON OFF
CLOCK
FILTER
2
3
CHECK TEST
PAR-F27MEA
TIMER SET
Check item
2
or more transmission line used?
M-NET Remote Controller
2
)
–37–
1Hr.
CENTRALLY CONTROLLED
˚C
ON OFF
D A I L Y
AUTO OFF
CLOCK
CHECK
REMAINDER
CHECK MODE
TEST RUN
STAND BY
˚C
LIMIT TEMP.
DEFROST
ERROR CODE
NOT AVAILABLE
TEMP
ON/OFF
CLOCK
ON OFF
PAR-F27MEA
TIMER SET
Trouble
Erroneous operation, error stop.
Erroneous operation, error stop.
Error stop in case multiple-core
cable is used.
Erroneous operation, error stop.
Not operate.
Not operate.
Error stop or not operate.
Never finish the initial mode.
Error stop or not operate.
Can not be properly set with power
source turned on.
Not operate.
Set temperature not obtained at
heating operations (Thermostat
stop is difficult)
Error stop.
Error stop, compressor trouble.