Mitsubishi Electric PQRY-P200YEM-A Service Handbook page 105

City multi
Table of Contents

Advertisement

(In the case of M-NET remote controller)
Symptom
1
Despite pressing of
1) M-NET transmission power source is not supplied
remote controller
ON/OFF switch,
operation does not
start and there is no
electronic sound.
(No powering signal
appears.)
2) Short circuit of transmission line.
3) Erroneous wiring of M-NET transmission line at outdoor unit.
4) Disconnection of transmission wiring at remote controller.
5) Faulty remote controller.
2
At about 10 seconds
1) Power source is not fed to indoor unit from transformer.
after turning remote
controller operation
switch ON, the
display distinguishes
and the operation
stops.
2) Faulty outdoor control circuit board uncontrolled.
Checking method & countermeasure
Check indoor LED3
Lighting?
Lighting
Check for the change of LED
display by operating dip switch
SW1 for self-diagnosis.
1 Check the transformer in accordance with the "TROUBLE SHOOTING" in the indoor unit's service handbook.
Cause
from outdoor unit.
1 Main power source of outdoor unit is not
connected.
2 Disconnection of connector on outdoor unit circuit
board.
Main board
: CNS1, CNVCC3
INV board
: CNAC2, CNVCC1, CNL2
3 Faulty power source circuit of outdoor unit.
• Faulty INV board,
• Blown fuse (F1 on INV board)
• Broken diode stack
• Broken resistor (R1) for rush current protection
1 Transmission line disconnection or slipping off from terminal
block.
2 Erroneous connection of indoor/outdoor transmission line to
TB7.
1 Main power source of indoor unit is not turned on.
2 Disconnection of connector (CND, CNT, CN3T) on indoor controller board.
3 Blown fuse on indoor controller board.
4 Faulty or disconnected transformer of indoor unit.
5 Faulty indoor controller board.
As normal transmission is fails between indoor and outdoor units, outdoor unit model can not be
recognized.
Check indoor unit
power source terminal
block voltage
AC 220~240V?
Extinguishing or
unable to confirm
Check fuse on circuit
board
Blown?
Check connection of con-
nector (CND, CNT, CN3T)
Disconnected
Check transformer
resistance value
Within rated?
Check self-diagnosis
function of outdoor unit
Changed?
Faulty indoor
controller board
a) Check transmission terminal block of
remote controller for voltage.
i) In case of 17 ~ 30V
ii) In case of less than 17V
NO
Check main power source
of power source wiring.
YES
Check 220V~240V
YES
circuit for short circuit
and ground fault.
NO
YES
Improper connector
connection
NO
1
Check cause of trans-
former disconnection.
NO
•Ground fault on circuit
board
•Ground fault on
YES
sensor, LEV
NO
Check self-diagnosis function af-
ter powering outdoor unit again.
Changed?
YES
Faulty outdoor unit
control circuit board
YES
Accidental
trouble
–104–
Checking method & countermeasure
→ Faulty network remote controller
→ See "Transmission Power Circuit
(30V) Check Procedure".
The cause of 2) and 3) is
displayed with self-diagnosis
LED for 7102 error.
Apply power
source again.
NO
Repair
faulty point.