Mitsubishi Electric PQRY-P200YEM-A Service Handbook page 127

City multi
Table of Contents

Advertisement

Checking
code
6607
No ACK error
System
Generating
Display of
compo-
unit address
trouble
sition
1 Outdoor
Remote
unit (OC)
controller
(RC)
2 BC
Remote
controller
controller
<master>
(RC)
(BC)
3 BC
Remote
controller
controller
<slave>
(RC)
(BS)
4 Indoor
Remote
unit (IC)
controller
(RC)
5 Remote
Remote
controller
controller
(RC)
(RC)
Meaning, detecting method
When no ACK signal is detected in 6 continuous times with 30 second interval by
transmission side controller, the transmission side detects error.
Note:
The address/attribute shown on remote controller indicates the controller
not providing the answer (ACK).
Detecting
method
No reply
1) Poor contact of transmission line of OC or BC.
(ACK) at
2) Damping of transmission line voltage/signal
OC
by acceptable range of transmission wiring
transmis-
exceeded.
sion to BC
Farthest
Remote controller wiring : Less than 10m
3) Erroneous sizing of transmission line (Not
within the range below).
Wire diameter
4) Faulty control circuit board of OC.
No reply
1) When BC controller (master) address is
(ACK) at
changed or modified during operation.
BC <master>
2) Faulty or disconnection of transmission wir-
transmis-
ing of BC controller (master).
sion to IC
3) Slipping off of BC unit connector (CN02).
4) Faulty BC controller (master) circuit board.
No reply
1) When BC controller (slave) is changed or
(ACK) at
modified during operation.
BC <slave>
2) Faulty or disconnection of transmission wir-
transmis-
ing of BC controller (slave).
sion to BC
3) Slipping off of BC unit connector (CN02).
<master>
4) Faulty BC controller (slave) circuit board.
No reply
1) When IC unit address is changed or modified
(ACK) at IC
during operation.
transmis-
2) Faulty or disconnection of transmission wir-
sion to RC
ing of IC.
3) Slipping off of IC unit connector (CN2M).
4) Faulty IC unit controller.
5) Faulty remote controller.
No reply
1) Faulty transmission wiring at IC unit side.
(ACK) at
2) Faulty transmission wiring of RC.
RC
3) When remote controller address is changed
transmis-
or modified during operation.
sion to IC
4) Faulty remote controller.
Cause
: Less than 200m
: 1.25mm
2
or more
–126–
Checking method & countermeasure
Shut down OC unit power source, and
make it again.
It will return to normal state at an ac-
cidental case.
When normal state can not be re-cov-
ered, check for the 1) ~ 4) of the cause.
Shut down both OC and IC power so-
urces simultaneously for 5 minutes or
more, and make them again.
It will return to normal state at an acci-
dental case.
When normal state can not be re-cov-
ered, check for the 1) ~ 4) of the cause.
Shut down both OC and master BC
power sources simultaneously for 5 min-
utes or more, and make them again.
It will return to normal state at an acci-
dental case.
When normal state can not be re-cov-
ered, check for the 1) ~ 4) of the cause.
Shut down both OC and IC power so-
urces simultaneously for 5 minutes or
more, and make them again.
It will return to normal state at an acci-
dental case.
When normal state can not be re-cov-
ered, check for the 1) ~ 4) of the cause.
Shut down OC power sources for 5 min-
utes or more, and make it again.
It will return to normal state at an acci-
dental case.
When normal state can not be re-cov-
ered, check for the 1) ~ 4) of the cause.