Download Print this page

Panasonic KT4R Communication Instruction Manual page 50

Temperature controller
Hide thumbs Also See for KT4R:

Advertisement

Modbus
Function
Code
03/06H
0040H
03/06H
0041H
03/06H
0042H
03/06H
0043H
03/06H
0044H
03/06H
0045H
03/06H
0046H
03/06H
0047H
03/06H
0048H
03/06H
006FH
6.2.2 A Single Piece of Data Write Command
Modbus
Function
Code
06H
0070H
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Data Item
EV1 alarm Energized/De-energized
EV2 alarm Energized/De-energized
Not used
(*1)
Not used
(*1)
Input type
Direct/Reverse action
Not used
(*1)
AT bias
ARW
Reserved
(*9)
Data Item
Key operation change flag clearing
0000H : Energized
0001H : De-energized
0000H : Energized
0001H : De-energized
0000H : K -200 to 1370
0001H : K -200.0 to 400.0
0002H : J -200 to 1000
0003H : R 0 to 1760
0004H : S 0 to 1760
0005H : B 0 to 1820
0006H : E -200 to 800
0007H : T -200.0 to 400.0
0008H : N -200 to 1300
0009H : PL-
000AH : C(W/Re5-26) 0 to 2315
000BH : Pt100
000CH : JPt100 -200.0 to 500.0
000DH : Pt100
000EH : JPt100 -200 to 500
000FH : K -328 to 2498
0010H : K -328.0 to 752.0
0011H : J -328 to 1832
0012H : R 32 to 3200
0013H : S 32 to 3200
0014H : B 32 to 3308
0015H : E -328 to 1472
0016H : T -328.0 to 752.0
0017H : N -328 to 2372
0018H : PL-
0019H : C(W/Re5-26) 32 to 4199
001AH : Pt100
001BH : JPt100 -328.0 to 932.0
001CH : Pt100
001DH : JPt100 -328 to 932
001EH : 4 to 20 mA DC -2000 to 10000
001FH : 0 to 20 mA DC -2000 to 10000
0020H : 0 to 1 V DC
0021H : 0 to 5 V DC
0022H : 1 to 5 V DC
0023H : 0 to 10 V DC
0000H : Reverse action
0001H : Direct action
Set value, Decimal point ignored
Set value
0001H : Clear key operation change flag
(*10)
Data
0 to 1390
-200.0 to 850.0
-200 to 850
32 to 2534
-328.0 to 1562.0
-328 to 1562
-2000 to 10000
-2000 to 10000
-2000 to 10000
-2000 to 10000
Data

Advertisement